User Manual
16–10 PCCC Host Commands
Publication 2755-833
1
3
0
2
STS= 00H
TNS
High Byte Low Byte
MSB LSB
Reply
CMD Reply = 48H
5
1
3
2
4
0
STS= 00H
Command Address = 600H through 639H,640H, 641H
TNS
High Byte Low Byte
LSB
CMD= 08H
Execute Decoder Function
MSB
If you send a command with an invalid address, the reply returns a
status code of 10H (invalid address).
To set the current configuration to the factory defaults, send this
command:
2
4
0
5
1
3
STS= 00H
Command Address = 633H
TNS
High Byte Low Byte
MSB LSB
CMD= 08H
S
et
D
eco
d
er
Configuration
to
D
efaults
To save the current configuration and restart the decoder, send this
command:
5
1
3
2
4
0
STS= 00H
Command Address = 632H
TNS
High Byte Low Byte
MSB LSB
CMD= 08H
S
a
v
e
Configuration
an
d R
estart
D
eco
d
er
To clear output counter 4 to all zeros, send this command:
5
1
3
2
4
0
STS= 00H
Command Address = 610H
TNS
High Byte Low Byte
MSB LSB
CMD= 08H
Clear
O
utput
Counter
4