User Manual

7–15Configuration: Scanner Control, Primary Match Table, Discrete I/O
Publication 2755-833
Discrete I/O Parameters
These parameters define conditions that control the discrete outputs.
Each output is defined by four parameters:
normal state of an output (O=opened or C=closed)
source of the event (Scanner A or B)
condition that activates an output
duration of pulsed output
send Host Message parameter
The discrete outputs can be controlled locally via the configuration
screens or remotely using host commands. The discrete I/O system
can:
indicate the success or failure of the decoder to read bar code data
from a package
indicate the results of a compare operation between decoded bar
code data and match code data
provide external control of the outputs using host commands
indicate a buffer full condition (no data lost)
indicate a buffer overflow condition
load bar code data into the match code table using an external
switch along with an input module
!
ATTENTION: When controlling outputs locally using
configuration screens, suspend host communications to
prevent outputs from unintentionally changing state.
Each discrete I/O parameter is defined below. The options for each
parameter are shown, with the default setting in bold letters.
Output State
Field Type Options
Select
O = Normally Open
C = Normally Closed
Defines the normal state of each discrete output (or input). The
default is O=Normally Opened. To change the state of the output to
C=Normally Closed, select C.