Junction Box Cable Pinout Description
* For connection to MobileView Guard G750 Terminals only.
K1, 17-pin
Circular
Jack Pin #
Junction Box
Cable
Wire Color
K2, 8-pin
RJ-45
Jack
K3, 12-pin
Terminal
Block
Description
1pink
-->> - 1 24V dc
2black
-->> - 2 GND_IN
3 green-brown
-->> - 3 E-stop, circuit 1, positive*
4 white-green
-->> - 4 E-stop, circuit 1, negative*
5 grey-pink
-->> - 5 E-stop, circuit 2, positive*
6 red-blue
-->> - 6 E-stop, circuit 2, negative*
7brown
-->> - 7 Enabling switch, circuit 1, positive*
8yellow
-->> - 8 Enabling switch, circuit 1, negative*
12 green
-->> - 9 Enabling switch, circuit 2, positive*
17 grey
-->> - 10 Enabling switch, circuit 2, negative*
9-
-->> - - Not used
10 -
-->> - 12 Not used
11 violet
-->> - 11 Not used
13 blue
-->> 1 - TD+ (transmit)
14 white
-->> 2 - TD- (transmit)
15 orange
-->> 3 - RD+ (receive)
16 red
-->> 6 - RD-(receive)