Terminal Connections Chapter 6
Software and Firmware Requirements
The software and firmware must be installed on the development computer and
the PanelView Plus 6 terminal to configure and communicate with an
Allen-Bradley controller on a ControlNet network.
Table 72 - ControlNet Unscheduled Communication
Software/Firmware Minimum Version
FactoryTalk View Studio 6.0 or later
FactoryTalk View Machine Edition Runtime 6.0 or later
ControlNet module firmware 2711P-RN15S, Series A, Rev A (firmware revision 2.07 or
later)
(1)
(1) This applies to terminals that are ordered as pre-configured units with the ControlNet module.
Table 73 - ControlNet Scheduled Communication
Requirements Minimum Version
FactoryTalk View Studio 6.0 or later
FactoryTalk View Machine Edition Runtime 6.0 or later
RSNetWorx
for ControlNet 5.11 or later
Studio 5000 21.00.00 or later
ControlNet module firmware 2711P-RN15S, Series A, Rev C (firmware revision 3.08 or
later)
(1)
(1) This applies to terminals that are ordered as preconfigured units with the ControlNet module.
WARNING: The ControlNet communication module, cat. no. 2711P-RN15S or
2711P-RN15SK, does not run with FactoryTalk View ME firmware revision
3.20.04 or earlier. All ControlNet modules with revision 3.07 firmware must be
upgraded to revision 3.08 or later; otherwise, outputs can turn on an
indeterminate state.