User Manual PanelView Plus 6 HMI Terminals 400, 600, 700, 1000, 1250, 1500
Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices.
Summary of Changes This manual contains new and updated information. Changes throughout this revision are marked by change bars, as shown to the right of this paragraph. New and Updated Information This table contains the changes made to this revision. Most of the updates are the result of adding the new generation PanelView™ Plus 6 - 400 and 600 terminals to the publication.
Summary of Changes Notes: 4 Rockwell Automation Publication 2711P-UM006C-EN-P - April 2013
Table of Contents Summary of Changes Preface Important User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 New and Updated Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Package Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents Configure Print Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Check Integrity of Application Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Configure Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . View and Clear the System Event Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents Chapter 6 Terminal Connections USB Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ethernet Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Serial Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DH-485/DH+ Communication Module . . . . . . . . . . . . . . . . . . . . . . . . . ControlNet Communication Module . . . . . .
Table of Contents Notes: 8 Rockwell Automation Publication 2711P-UM006C-EN-P - April 2013
Preface This manual describes how to install, configure, operate, and troubleshoot PanelView Plus 6 terminals. It does not provide procedures on how to create applications that run on the terminal. You also need to do the following: • Use FactoryTalk® View Studio for Machine Edition software to create an HMI application to run in the terminal. • Create ladder logic to interact with the HMI application.
Preface Notes: 10 Rockwell Automation Publication 2711P-UM006C-EN-P - April 2013
Chapter 1 Overview About the Terminals Topic Page Windows CE Operating System 12 Open versus Closed System 12 Desktop Access 13 Software Support 13 400 and 600 Terminal Features 14 700 to 1500 Terminal Features 17 400/600 Terminal Selections 20 700 to 1500 Terminal Selections 21 Accessories 22 PanelView Plus 6 terminals are operator interface devices that run HMI machine-level applications in an industrial environment. The displays range in size from 4 to 15-inches.
Chapter 1 Overview PanelView Plus 6 terminals run the Windows CE operating system (OS), providing the foundational OS elements for the majority of user needs. Windows CE Operating System For users with more complex application requirements, some of the terminals offer optional, extended features and file viewers. Table 1 - Operating System Features Features 400 Terminals Cat. Nos.
Overview Chapter 1 You can configure the terminal to perform one of three actions at startup: • Launch a FactoryTalk View Machine Edition HMI application. • Launch the FactoryTalk View Machine Edition Configuration mode of the terminal where you load and run applications, configure start-up options and terminal settings, and enable or disable desktop access. • Launch the Windows Explorer desktop.
Chapter 1 Overview Both the 400 and 600 terminals provide these communication options: • RS-232 serial port only or • Ethernet port and RS-232 serial port 400 and 600 Terminal Features Figure 1 - 400 Keypad or Keypad/Touch Terminals 1 12 11 10 9 2 8 3a 7 6 4 5 Table 3 - PanelView Plus 6 - 400 Terminal Components Item Component 1 3.5-in.
Overview Chapter 1 Figure 2 - 600 Touch Terminals 1a 12 11 3b 10 9 2 3a 8 7 6 4 5 Figure 3 - 600 Keypad or Keypad/Touch Terminals 1b 12 F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 11 3b 2 10 9 3a 8 7 5 6 4 Table 4 - PanelView Plus 6 - 600 Terminal Components Item Component Item Component 1a 5.7-in. color or grayscale display with a touch screen 6 RS-232 serial port for controller communication, printing, or file transfers 1b 5.7-in.
Chapter 1 Overview The terminals feature grayscale or color LCD displays with these input options. Table 5 - Operator Input Options Terminal Display Type 400 600 Keypad Touch Key and Touch Grayscale • Color • Grayscale • • • Color • • • • 1 2 3 5 F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 4 Table 6 - Display and Operator Input Features Item Feature Description 1 Product label Product identification label can be replaced with custom label.
Overview Chapter 1 The larger 700 to 1500 terminals consist of modular components ordered separately or as configured terminals. The modular components consist of the following: • Display module • Logic module • Optional communication module 700 to 1500 Terminal Features These components provide for flexible configuration, installation, and upgrades. You can order a factory-assembled unit with a single catalog number or separate components for field installation.
Chapter 1 Overview Configured Terminals A configured terminal, ordered as a single-catalog number, has a display module and logic module. An optional DH+/DH-485, ControlNet, or Ethernet communication module can be added later for additional network capabilities.
Overview Chapter 1 Operator Input All 700 to 1500 display modules have TFT color, graphic displays with either keypad, touch screen, or combination keypad/touch-screen input. Common features and firmware provide for easy migration to a larger display: • Eight-wire resistive touch screens are extremely accurate for operator interfaces. When a point on the touch screen is pressed, the layers connect and change the electrical current, which is then registered and processed.
Chapter 1 Overview 400/600 Terminal Selections Bulletin Input Type | Display Size | 2711P- | K = Keypad The table shows the catalog number breakdown for the 400 and 600 terminals. Display Type Communication | 4= 3.5 in. C = Color B = Keypad and Touch 6 = 5.7 in. Power | Operating System | 5 = RS-232, USB M = Grayscale 20 = Ethernet, RS-232, USB | A = AC 8 = Windows CE 6.0 D = DC 9 = Windows CE 6.
Overview The table shows the catalog number breakdown for the 700 to 1500 terminals. 700 to 1500 Terminal Selections Bulletin Input Type Display Size | | | 2711P- Chapter 1 K = Keypad 7 = 6.5 in. T = Touch 10 = 10.4 in. B = Keypad/Touch 12 = 12.1 in. Display Type Communication (1) Power Operating System | | | 4 = Ethernet, RS-232 & (2) USB A = AC 8= Windows CE 6.0 D = DC 9 = Windows CE 6.0 with extended features | C = Color Special Option | K = Conformal-Coated 15 = 15 in.
Chapter 1 Overview Table 14 - PanelView Plus 6 - 700 to 1500 Terminals with Extended Features Cat. Nos. Keypad Display Communication Memory (1) Input Power Touch Keypad/Touch Size Type RS-232 Ethernet RAM Nonvolatile 2711P-K7C4D9 2711P-T7C4D9 2711P-B7C4D9 6.5-in.
Overview Chapter 1 Table 15 - Display Modules - 700 to 1500 Terminals Cat. No. Input Type Display Marine Certified 2711P-RDK12C Keypad 12.1-in. color 2711P-RDK12CK Keypad 2711P-RDT12C Touch 2711P-RDT12CK Touch 2711P-RDT12H(1) Keypad/Touch 2711P-RDT12AG Touch 2711P-RDB12C Keypad/Touch 2711P-RDB12CK Keypad/Touch Conformal Coated Built-in Antiglare Overlay 1250 Model • • • • 1500 Model 2711P-RDK15C Keypad 15-in.
Chapter 1 Overview Table 18 - Secure Digital (SD) Cards Cat. No. Terminal Model Description 1784-SD1 1 GB Secure Digital (SD) card 1784-SD2 All terminals 2 GB Secure Digital (SD) card 2711C-RCSD USB to SD adapter for secure digital card (SD) Table 19 - CCFL Backlight Replacements (1) Cat. No.
Overview Chapter 1 Table 22 - Function Key Legend Kits Cat. No. Terminal Model(1) 2711P-RFK6 600 keypad 2711P-RFK7 700 keypad 2711P-RFK10 1000 keypad 2711P-RFK12 1250 keypad 2711P-RFK15 1500 keypad Description Blank legend inserts and software (1) Applies to keypad and keypad/touch-screen terminals. Table 23 - Mounting Hardware Cat. No.
Chapter 1 Overview Table 27 - Bezel Replacements Cat. No. Terminal Model 2711P-RBK10 Operator Input Keypad Touch Key/Touch • 2711P-RBT10 1000 • 2711P-RBB10 • 2711P-RBK12 • 2711P-RBT12 2711P-RBT12H • 1250 (1) • 2711P-RBB12 • 2711P-RBK15 • 2711P-RBT15 1500 • 2711P-RBB15 • (1) Applies to the cat. no. 2711P-RDT12H 1250 high-bright display module. Table 28 - Adapter Plates Cat. No.
Chapter 2 Install Terminal Topic Page Required Circuit Parameters for USB Peripheral Devices 29 Mounting Clearances 30 Panel Guidelines 30 Panel Cutout Dimensions 30 Remove and Install the Power Terminal Block 37 Mount the 400/600 Terminal in a Panel 33 Mount the 700 to 1500 Terminal in a Panel 35 Remove and Install the Power Terminal Block 37 DC Power Connections 38 AC Power Connections 41 Initial Startup 43 Reset the Terminal 43 ATTENTION: Environment and Enclosure This equipm
Chapter 2 Install Terminal North American Hazardous Location Approval The following information applies when operating this equipment in hazardous locations. When marked, these products are suitable for use in "Class I, Division 2, Groups A, B, C, D"; Class I, Zone 2, Group IIC, Class II, Division II, Groups F, G; Class III hazardous locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code.
Install Terminal Chapter 2 Required Circuit Parameters for USB Peripheral Devices The terminals contain one or two USB host ports that comply with hazardous location environments. Field-wiring compliance requirements are provided in compliance with the National Electrical Code, Article 500.
Chapter 2 Install Terminal Mounting Clearances Plan for adequate space around the terminal, inside the enclosure, for ventilation and connections. Consider heat produced by other devices in the enclosure. The ambient temperature around the terminal must be 0…55 °C (32…131 °F). Table 31 - Minimum Required Clearances Product Area Minimum Clearance Top 51 mm (2 in.) Bottom 102 mm (4 in.) Side 25 mm (1 in.) Back 0 mm (0 in.) A clearance of 102 mm (4 in.
Install Terminal Product Dimensions Chapter 2 Table 33 and Table 34 provide product dimensions for all PanelView Plus 6 terminals. Figure 5 - PanelView Plus 6 - 400 Keypad or Keypad/Touch a c d b Figure 6 - PanelView Plus 6 - 600 Touch a c d b Figure 7 - PanelView Plus 6 - 600 Keypad or Keypad/Touch a F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 1 d c 6 6 1 6 1 b Table 33 - PanelView Plus 6 - 400 and 600 Product Dimensions Height (a) mm (in.) Width (b) mm (in.) Depth (c) mm (in.
Chapter 2 Install Terminal The 700 to 1500 terminals look similar. The 1000 keypad and keypad/touch terminals are shown for illustrative purposes. Figure 8 - PanelView Plus 6 - 1000 Keypad, Keypad/Touch, Touch a a b b c c d d Table 34 - PanelView Plus 6 - 700 to 1500 Terminal Dimensions Terminal Input Type Height (a) mm (in.) Width (b) mm (in.) Depth (c) Display to Logic Module mm (in.) Depth (d) Display to Comm Module mm (in.) 700 Keypad or keypad/touch 193 (7.58) 290 (11.40) 55 (2.
Install Terminal Mount the 400/600 Terminal in a Panel Chapter 2 The terminals were designed for single-person installation. No tools are required except for those needed to make the panel cutout Mounting levers secure the terminal to the panel. Four or six levers are required depending on the terminal model. The levers insert into the mounting slots on the top and bottom of the terminal. Each mounting slot has six notches with alignment marks that are locking positions for a lever.
Chapter 2 Install Terminal 3. Place the terminal in the panel cutout. F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 4. Insert all mounting levers into the mounting slots on the terminal. Slide each lever until the flat side of the lever touches the panel surface. Flat Side of Lever Mounting Levers Mounting Slots 5. When all levers are in place, slide each lever an additional notch or two until you hear a click.
Install Terminal Mount the 700 to 1500 Terminal in a Panel Chapter 2 Mounting clips secure the 700 to 1500 terminals in a panel. The number of clips varies by terminal size. Tools required for installation include panel cutout tools, a small, slotted screwdriver, and a torque wrench for tightening the mounting clips. ATTENTION: Disconnect all electrical power from the panel before making the panel cutout.
Chapter 2 Install Terminal 3. Place the terminal in the panel cutout. Mounting Clip Mounting Clip Slot 4. Slide the ends of the mounting clips into the slots on the terminal. 5. Tighten the mounting clip screws by hand until the gasket seal contacts the mounting surface uniformly. 6. Tighten the mounting clips screws to a torque of 0.90…1.1 N•m (8…10 lb•in) by using the specified sequence, making sure not to overtighten.
Install Terminal Remove and Install the Power Terminal Block Chapter 2 The terminals are shipped with a power terminal block installed. You can remove the terminal block for ease of installation, wiring, and maintenance. WARNING: Explosion Hazard If you connect or disconnect wiring while the power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed and the area is nonhazardous before proceeding.
Chapter 2 Install Terminal 700 to 1500 Terminals Follow these steps to remove the terminal block from a 700 to 1500 terminal. 1. Loosen the two screws that secure the terminal block. 2. Gently pull the terminal block away from the connector. Three-position AC Terminal Block Two-position DC Terminal Block Follow these steps to install the terminal block. 1. Reattach the terminal block to the connector until seated. 2. Tighten the two screws that secure the terminal block to a torque of 0.40…0.51 N•m (3.
Install Terminal Chapter 2 PanelView Plus 6 devices were tested to operate with the catalog number 2711P-RSACDIN power supply. To use another power supply, review the criteria in the table. Table 38 - Power Supply Criteria If the PanelView Plus 6 Device Use a Description Connects to equipment with isolated communication ports SELV or PELV power supply Other equipment can share this power supply with the PanelView Plus 6 device provided that no ground loops are created.
Chapter 2 Install Terminal Connect DC Power WARNING: Explosion Hazard Do not disconnect equipment unless power has been switched off and area is known to be nonhazardous. Disconnect all power before installing or replacing components. Failure to disconnect power can result in electrical shock or damage to the terminal. Follow these steps to connect the terminal to DC power. 1. Verify that the terminal is not connected to a power source. 2. Strip 7 mm (0.28 in.) of insulation from the ends of the wires.
Install Terminal AC Power Connections Chapter 2 Terminals with an integrated AC power supply have these power ratings. Table 40 - AC Power Ratings Terminal Input Voltage Power Consumption 400, 600 100…240V AC (50…60 Hz) 35VA max 700, 1000, 1250, 1500 85…264V AC (47…63 Hz) 160VA max Protective Earth and Functional Earth Connections PanelView Plus 6 devices with an AC power input have a protective earth terminal you must connect to a low-impedance earth ground.
Chapter 2 Install Terminal Connect AC Power WARNING: Explosion Hazard Do not disconnect equipment unless power has been switched off and area is known to be nonhazardous. Disconnect all power before installing or replacing components. Failure to disconnect power can result in electrical shock or damage to the terminal. ATTENTION: Improper wiring of the power terminals can result in voltage at the communication connector shells. Do not apply power to the terminal until all wiring is connected.
Install Terminal Initial Startup Chapter 2 The first time you start the system, the terminal goes through its power-up sequence and launches FactoryTalk View ME Station Configuration mode. You can change the action the terminal takes on startup by pressing Terminal Settings then choosing Startup Options. You can configure one of these options: • Launch a FactoryTalk Machine Edition HMI application that is configured to run at startup.
Chapter 2 Install Terminal After a restart, the terminal performs a series of start-up tests then takes one of these actions: • Launches an HMI application that is configured to run at startup. • Launches FactoryTalk Machine Edition Configuration mode. • Launches the Windows Explorer desktop. The action that occurs depends on the start-up options configured for your terminal. Refer to Start-up Options on page 51 for details.
Chapter 3 Configuration Mode Topic Page Topic Page Access Configuration Mode 45 Configure Print Options 72 Terminal Settings 48 Check Integrity of Application Files 74 Load and Run Application 50 Configure Diagnostics 75 Start-up Options 51 View and Clear the System Event Log 76 Desktop Access 54 System Information 76 Communication Setup 58 Enable or Disable the Alarm Display 78 Ethernet Network Connections 60 Time and Date Settings 79 File Management 64 Regional Setting
Chapter 3 Configuration Mode Figure 10 - FactoryTalk View ME Station Configuration Mode Dialog Box Name of application that is currently loaded. Appears only if application is loaded. Displays network information every 60 seconds. If the network is shutdown the IP address and subnet mask appear as 0.0.0.0. Table 42 - Configuration Mode Operations Terminal Operation Description Load Application (F1) Opens a dialog box where you select an application to load.
Configuration Mode Chapter 3 Input Panel When you activate a data entry field, the input panel opens. If the field is restricted to a numeric value or IP address, then only the 0…9 and decimal point keys are enabled. Figure 11 - Input Panel Display Area Character Keyboard Controls Table 44 - Input Panel Controls Input Panel Controls Function SHF Switches keys between their shifted and unshifted state. The initial default is unshifted. CAP Switches keys between lowercase and uppercase characters.
Chapter 3 Configuration Mode You can modify settings on the terminal that are not specific to the application. Terminal Settings 1. Press Terminal Settings from the FactoryTalk View ME Station Configuration mode dialog box. Moves selection bar up or down. Accesses settings for selected function. Closes dialog box and returns t to previous dialog. 2. Select a function by using the up and down cursor buttons: • On touch-screen terminals, press the button.
Configuration Mode Chapter 3 Figure 12 - Terminal Settings Menu Structure Alarms Diagnostics Setup page 78 page 75 Display Display Intensity Display Temperature page 67 Desktop Access Cursor Screen Saver page 68 page 67 page 68 page 54 File Management Copy Files Delete Files Copy Applications Font Linking Delete Fonts Delete Applications Copy Fonts page 64 page 66 page 66 Delete Log Files page 65 page 64 page 84 Input Devices Mouse Keyboard/Keypad page 69 Touch Screen String Po
Chapter 3 Configuration Mode Load and Run Application Before running a FactoryTalk View Machine Edition .mer application, you must first load the application. You can load an .mer application from internal storage or nonvolatile memory in the terminal, an SD card, or a USB flash drive. List of FactoryTalk View .mer applications stored in terminal memory. Moves Highlight Up Moves Highlight Down Follow these steps to load and run an application. 1.
Configuration Mode Start-up Options Chapter 3 You can specify what action the terminal takes on startup or a reset. This Start-up Option Performs This Action Typical System Do not start FactoryTalk View ME Station Launches the Windows Explorer desktop on startup. Open Go to Configuration Mode Launches FactoryTalk View ME Station Configuration Closed mode on startup. This is the initial, factory default setting.
Chapter 3 Configuration Mode Enter Configuration Mode on Startup Follow these steps to automatically launch the FactoryTalk View ME Station Configuration mode dialog box on startup. 1. Press Terminal Settings>Startup Options. 2. Press On Startup to select Go to Configuration Mode. 3. Press Configuration Mode Options. 4. Press Load Current Application to specify whether you want to load the current application on startup. 5.
Configuration Mode Chapter 3 Run the Loaded Application on Startup Follow these steps to run the FactoryTalk View .mer application currently loaded in the terminal on startup. This is typical when running a closed system. 1. Press Terminal Settings>Startup Options. 2. Press On Startup to select Run Current Application. If an application is not loaded, the options are disabled. 3.
Chapter 3 Configuration Mode Desktop Access You can allow or restrict access to the Windows desktop on all terminals. From the desktop, you can perform system and control panel operations, or run thirdparty applications. Terminals with extended features can additionally run viewers, media players, and launch the web browser. You can allow access temporarily to perform specific tasks, then disable desktop access to prevent unauthorized changes.
Configuration Mode Chapter 3 5. Press OK to exit Desktop Access Management, then Close to exit Terminal Settings. 6. Press Exit from FactoryTalk View ME Station Configuration mode to access the desktop. With desktop access set to allow, you are not required to enter a password.
Chapter 3 Configuration Mode Set a Desktop Password IMPORTANT If you disallow or restrict access to the desktop, you are required to set a password along with a challenge question. Follow these steps to set a new password. 1. Press Set Password from Desktop Access Management. 2. Press Set Password and enter an 8…20 character password, then press Enter. TIP You must correctly enter this password before accessing the desktop. 3.
Configuration Mode Chapter 3 Reset the Desktop Password To clear the current password and reset a new password, you must first correctly respond to the current challenge question. If you cannot remember the response, you have to restore the terminal to its factory default settings. Refer to Access Maintenance Operations on page 170 . IMPORTANT You can clear and reset the password and challenge question if access to the desktop is restricted or set to disallow.
Chapter 3 Configuration Mode Communication Setup You configure communication for your application and controller by using RSLinx Enterprise software: • Access KEPServer Serial Port IDs. • Edit the driver settings for the protocol used by your .mer application. • Edit the device address of the controller on the network. Configure KEPServer Serial Port IDs To access KEPServer serial communication, you must have KEPServer Enterprise installed on your terminal.
Configuration Mode Chapter 3 Table 46 - Communication Driver Properties Field Description Valid Values Use Auto Config Automatically or manually configures the baud rate, parity, and error checking parameters. Yes (auto configure) No (manual configure) Device The serial device terminal is connected to. PLC-5®, SLC™, MicroLogix™, Logix Platform Error Check Type of error checking used. Error checking is automatically configured if Use Auto Config is set to Yes.
Chapter 3 Configuration Mode Configure a Device Address Follow these steps to edit the address of a device such as a logic controller. 1. From the RSLinx Configuration dialog box, select a device node. 2. Press Edit Device to view the device name and current address. 3. Press Device Address to modify the address. The input panel opens with the current address. 4. Use the Input Panel to modify the address and then press Enter. You return to the previous dialog box with the new address. 5. Press OK.
Configuration Mode Chapter 3 Follow these steps to view or enter the IP address of your terminal. 1. Press Terminal Settings>Networks then Communications>Network Connections>Network Adapters. 2. Press IP Address to view or modify the IP address. 3. Press Use DHCP to enable or disable DHCP assignment of addresses: • If DHCP is enabled or set to Yes, IP address are automatically assigned. • If DHCP is disabled, you can manually enter IP address.
Chapter 3 Configuration Mode Set the Ethernet Link Speed You can set the speed and duplex setting of the Ethernet link. TIP Link settings for the 2711P-RN20 Ethernet module cannot be set in FactoryTalk View Machine Edition Station. The module is set to automatically sense the settings on the network. 1. Press Terminal Settings>Networks then Communications>Network Connections>Network Adapters. 2. Press Settings to view or modify the Ethernet link settings. 3.
Configuration Mode Chapter 3 Follow these steps to define a name server address. 1. Press Terminal Settings>Networks then Communications>Network Connections>Network Adapters. 2. Press Name Servers. 3. Press the following fields to enter a name server address. Field Description Valid Values Primary DNS The address of the primary DNS resolver. xxx.xxx.xxx.xxx Secondary DNS The address of the secondary DNS resolver. xxx.xxx.xxx.xxx Primary WINS The address of the primary WINS resolver. xxx.xxx.
Chapter 3 Configuration Mode Authorize Terminal to Access Network Resources The terminal can access network resources with proper identification. A user name, password, and domain must be provided by your network administrator. 1. Press Terminal Settings>Network then Communications>Network Connections>Network Identification. 2. Press user name, password, and domain to enter the information provided by your network administrator.
Configuration Mode Chapter 3 2. Press Source to select the storage location of the application or font file you want to delete: • Internal Storage - nonvolatile memory of the terminal • External Storage 1 - SD card loaded in the card slot of the terminal • External Storage 2 - USB flash drive connected to a USB host port 3. Select a file from the list. 4. Press Delete. 5. Select Yes or No when asked if you want to delete the selected application or font file from the storage location.
Chapter 3 Configuration Mode Copy Application File or Font File You can copy FactoryTalk View ME Station application .mer files or font files from one storage location to another in the terminal. The procedure for copying an application file or a font file between storage locations is the same. 1. Press Terminal Settings>File Management>Copy Files>Copy Applications or Copy Fonts. List of files stored in nonvolatile memory of terminal. 2.
Configuration Mode Display Settings Chapter 3 For the terminal display, you can adjust its intensity, view its temperature, configure the screen saver, or enable/disable the screen cursor. Adjust the Display Intensity You can modify the intensity of the terminal backlight. You can use the default intensity of 100% or you can change the intensity for runtime operations. 1. Press Terminal Settings>Display>Display Intensity. 2.
Chapter 3 Configuration Mode Configure the Screen Saver The screen saver on the terminal activates after an idle period at a specific intensity. The default idle timeout is 10 minutes. You can adjust the idle timeout and intensity level for the screen saver, disable the screen saver, and enable or disable the screen saver bitmap. 1. Press Terminal Settings>Display>Screen Saver. 2. Press Screen Saver to select an idle timeout for activating the screen saver.
Configuration Mode Input Device Settings Chapter 3 You can adjust the settings for input devices used by the terminal including the keypad, attached keyboard, mouse, touch screen, and string entry popup. Configure Keyboard or Keypad Settings You can adjust settings for keys on an attached keyboard or the terminal keypad. 1. Press Terminal Settings>Input Devices>Keyboard/Keypad. 2. Press Repeat Rate to specify the number of times a key is repeated per second when you hold a key down.
Chapter 3 Configuration Mode Change the Popup for String Entry You can specify whether to use the standard input panel for data entry or a string popup. The popup keyboard is the default. 1. Press Terminal Settings>Input Devices>String Popup. 2. Press Invoke pop-up character input instead of popup keyboard to select the preferred input method for string entry. 3. Press OK. Calibrate a Touch Screen Follow these steps to calibrate the touch screen.
Configuration Mode Chapter 3 Set Double-tap Sensitivity for a Touch Screen You can set and test the sensitivity for both the speed and physical distance between touch-screen presses. The process is identical to setting the double-click sensitivity for the mouse. 1. Press Terminal Settings>Input Devices>Touch Screen>Double Tap Sensitivity. 2. Double-tap Set to set the sensitivity of touch-screen presses. 3. Double-tap Test to test the sensitivity of touch-screen presses.
Chapter 3 Configuration Mode Configure Print Options You can configure settings for printing displays, alarm messages, or diagnostic messages from FactoryTalk View ME Station applications. The setup for printing displays and messages is the same; advanced settings are different. PanelView Plus 6 terminals are shipped with support for a large selection of Canon, Epson, Hewlett-Packard, and Brother Printers.
Configuration Mode Chapter 3 3. Press Advanced to access additional settings: • Advanced settings for printing displays include these: – Print orientation (portrait or landscape) – Draft mode (enable or disable) – Color (yes or no) • Advanced settings for printing diagnostic and alarm messages determines when to print messages sent to the network or USB port.
Chapter 3 Configuration Mode Check Integrity of Application Files Periodically check the integrity of the FactoryTalk View ME Station application that is loaded in the terminal and the runtime files. Al l errors, warnings, and information messages generated by these files are logged to a file. You can periodically view the log and clear all items from the log. 1. Press Terminal Settings>File Integrity Check. 2.
Configuration Mode Configure Diagnostics Chapter 3 You can configure diagnostics for a target computer. To access diagnostics, press Terminal Settings>Diagnostic Setup from the Configuration Mode dialog box. You see a tree view of diagnostic nodes. To access the Remote Log Setup or Message Routing, select the node and then press Edit. The Remote Log Destination forwards received messages to a Windows computer running diagnostics. The location is determined by the IP address and port number.
Chapter 3 Configuration Mode View and Clear the System Event Log The System Event Log dialog box displays warnings, errors, and events logged by the terminal. The log provides a time stamp of when each event occurred and text describing the event. If the event log is full when a new event occurs, the oldest entry is removed to accommodate the new event. 1. Press Terminal Settings>System Event Log. 2. Select an event and press More Details to display log details for that event. 3.
Configuration Mode Chapter 3 • The CPU temperature must be less than 95 °C (203 °F). • The battery voltage must be at least 2.75V DC. Battery State Description Good Good battery condition. Failing Low battery. Replace the battery. Bad Battery is missing or bad. Replace the battery. 2. Press Memory Allocation to view the following: • Amount of allocated storage or program memory • Amount of storage or program memory in use • Amount of available nonvolatile memory 3.
Chapter 3 Configuration Mode Display FactoryTalk View ME Station Information You can display the firmware and version information for installed system components on your terminal and technical support information. 1. Press Terminal Settings>System Information>About FactoryTalk View ME Station. 2. Press Technical Support to display the support phone number and website for your terminal. 3. Press Close until you return to terminal settings.
Configuration Mode Time and Date Settings Chapter 3 You can change the date, time, time zone, and regional settings for terminal operations. Change the Date for Terminal Operations Follow these steps to adjust the date for terminal operations. 1. Press Terminal Settings>Time/Date/Regional Settings>Date. The current date appears in the Year, Month, and Day fields. 2. Press Year, Month, and Day to change the values. Field Description Valid Values Year The current year in a four-digit format.
Chapter 3 Configuration Mode Change the Time Zone for Terminal Operations You can view or modify the current time zone that is installed on the terminal. Time zones are installed as a part of the operating system. Changing the time zone adjusts the current time and date to match the new time zone. 1. Press Terminal Settings>Time/Date/Regional Settings>Time Zone. 2. Press the up or down cursor to select a time zone.
Configuration Mode Regional Settings Chapter 3 You can adjust regional settings for a specific language installed on the terminal, including the date, time and numeric formats. Regional settings are accessed by pressing Terminal Settings>Time/Date/Regional Settings>Regional Settings. The current language is shown at the bottom of the Regional Settings dialo box. Select a Language Before you can modify regional settings for a language, you need to select a language installed on the terminal.
Chapter 3 Configuration Mode Change the Time Format for a Language Follow these steps to change the time format for the selected language. 1. Press Terminal Settings>Time/Date/Regional Settings>Regional Settings>Time Format. The current time is shown in the currently selected format. 2. Press the appropriate selections to adjust the formats.
Configuration Mode Chapter 3 Change the Short Date Format for a Language Follow these steps to change the short date format for the selected language. 1. Press Terminal Settings>Time/Date/Regional Settings>Regional Settings>Short Date Format. The Sample area shows the current date in the selected format. 2. Press Format to select an available format. The date is updated in the Sample area as you make selections. 3. Press Separator to change the separator for the date elements.
Chapter 3 Configuration Mode Font linking lets you run a translated application on the terminal by linking a font file to the base font (for example, linking a Chinese font file to the base font Arial). Font Linking For more details on preinstalled terminal fonts and additional fonts available for downloading, see Fonts Resident on Terminal on page 175. Press Terminal Settings>Font Linking to access this function. List of fonts loaded on the terminal.
Chapter 4 Windows CE Operating System Windows CE 6.0 Standard Features Topic Page Windows CE 6.0 Standard Features 85 Windows CE 6.
Chapter 4 Windows CE Operating System • VNC server and client viewer The platform distributes two VNC client viewers: – Vncviewer.exe in the \Windows folder on the terminal can be deployed to a personal computer for connecting, viewing, and controlling the Windows CE terminal (PanelView Plus 6). – Another viewer is available on the terminal to establish a VNC connection between two PanelView Plus 6 terminals. To access this VNC client, choose Start>Programs>VNC Viewer.
Windows CE Operating System Chapter 4 Server Support This table lists servers supported by the Windows CE 6.0 operating system. . Table 47 - Windows CE 6.0 Server Support Windows CE 6.0 with Extended Features Server Default State Description Web server Enabled The web server delivers content, such as web pages, by using the HTTP protocol over the Web. FTP server Enabled File Transfer Protocol (FTP) is a standard network protocol for exchanging files over the Internet (TCP/IP-based network).
Chapter 4 Windows CE Operating System Windows Explorer From the desktop, you can access Windows Explorer in several ways: • Open the My Device icon on the desktop. • Choose Start>Programs>Window Explorer. Besides the typical system folders, a few folders contain items specific to the PanelView Plus 6 terminals. Taskbar Folder Content Application Data Contains FactoryTalk View Machine Edition application files.
Windows CE Operating System Chapter 4 The Windows control panel is the desktop interface for configuring a terminal. You can set system-wide and terminal properties, such as network configuration, screen saver configuration, and touch screen calibration. Windows Control Panel Table 49 list the control panel applets. The language of the applets is based on the language set for the operating system. English is the default. TIP Most terminal settings are available in FactoryTalk View ME Station.
Chapter 4 Windows CE Operating System The Backup and Restore application lets you back up the current system image on the HMI terminal, then restore that image to the same terminal, or clone it to other terminals. This function is intended for OEMs who want to back up a terminal image, then clone or copy that same image to multiple terminals.
Windows CE Operating System Chapter 4 7. Click Backup to start the process. A progress bar shows the status of the backup. The backup can take a few minutes. You receive notification when the backup completes successfully. 8. Click OK. If the file exists, you are asked if you want to overwrite the current file. 9. Click Exit to close the Backup & Restore dialog box. . TIP You can verify that .
Chapter 4 Windows CE Operating System 8. Click Restore. The restore automatically includes advanced network and display settings if this option was checked when the backup was performed. 9. Click Yes to start the restore. The terminal starts the restore process. It can take a few minutes. IMPORTANT d Do not remove the USB flash drive or SD card, or power off the terminal during the restore. This could corrupt the firmware. If the restore fails, you need to reset the terminal from the maintenance menu.
Windows CE Operating System Hardware Monitor Chapter 4 The PanelView Hardware Monitor provides status and troubleshooting information for the terminals including running processes, system event log details, and monitoring of battery voltages, temperatures, and system usage, for example, CPU and memory loading. Processes The Processes tab of the Hardware Monitor shows all processes currently running on the PanelView Plus 6 terminal and memory usage of each process.
Chapter 4 Windows CE Operating System Monitors The Monitors tab of the PanelView Hardware Monitor provides continuous voltage, temperature, and load information for the terminal. Battery Voltage The Monitors tab gives a visual status and voltage reading of the battery for the real-time clock. The battery voltage is updated at powerup and then every hour. Table 51 - Battery Conditions Condition Logic Module Battery Depleted Less than 2.0V indicates a dead battery or no power. Low 2.0…2.
Windows CE Operating System Keypad Properties Chapter 4 Use the Keypad and Keyboard dialog boxes to adjust settings for the membrane keypad of your terminal or an attached USB keyboard. The Keyboard applet is always present. The Keypad applet appears only if your device has a keypad. If you attach two USB keyboards, settings are used that work with both keyboards.
Chapter 4 Windows CE Operating System Display Properties Use Display Properties to control the desktop background image and appearance, the brightness of the backlight, and screen saver settings. Desktop Background The Background tab in Display Properties controls the background bitmap on the desktop. The default bitmap is abclocknight. You can select another image from the pull-down menu or browse the system for a bitmap image. Custom images are in the \Windows folder.
Windows CE Operating System Chapter 4 Screen Saver The screen saver extends the lifetime of the display by dimming the backlight when the terminal is idle. The screen saver activates and displays a moving bitmap at a reduced brightness level after a continuous idle time. When the screen saver is deactivated, the display brightness returns to its normal level. The Screen Saver tab in Display Properties lets you perform these operations: • Enable the screen saver by using a specified idle timeout.
Chapter 4 Windows CE Operating System Logo Manager Use the Logo Manager to change the logo that appears on the splash screen at startup and the default screen saver image. The default image is the Allen-Bradley logo (ablogo.bmp). The logo can be a .bmp, .jpg, .gif, or .png image. For best results, it is recommended that the logo be created as a 90 x 90 pixel, 16-bit color image. Before applying the new logo, you can do the following: • Preview the logo on the splash screen.
Windows CE Operating System System Information Chapter 4 The System Information dialog provides tabs to let you view and set system-wide properties for your terminal. General Information The General tab of the System Information dialog box shows the current version of the Windows CE operating system, the processor type and speed, and RAM memory on terminal.
Chapter 4 Windows CE Operating System You have three options for handling the battery warning. Battery Warning Start-up Options Description Always show at startup (continue with startup) Shows the battery warning at startup with FactoryTalk View ME Station software running behind it. This is the default. Always show at startup (halt startup) Shows the battery warning at startup but halts the startup or boot process until you press OK. Never show at startup Hides the battery warning at startup.
Windows CE Operating System Chapter 4 Watchdog Errors You can show or hide watchdog errors at startup. Watchdog Error Options Description Always show watchdog errors at startup Shows the fatal watchdog error (error 02) at startup and halts the normal boot process. This is the default. The system launches the maintenance window with the watchdog error displayed. You can continue booting from this window. Refer to Access Maintenance Operations on page 170 for details.
Chapter 4 Windows CE Operating System User Accounts The User Accounts application lets you set up NTLM user accounts that can be used to authenticate client connections when using the FTP, web, and file servers. TIP NTLM is the authentication protocol used on networks that run Windows operating systems. A user account consists of a user name and password. Follow these steps to add a user account. 1. Double-click the User Accounts icon. . 2. Click in the user name field and type a name. 3.
Windows CE Operating System Chapter 4 Follow these steps to remove a user account. 1. Select a name in the user name list. 2. Click Remove user. 3. Click Yes to confirm the removal of the selected user account. The user account is permanently deleted from the user account list. 4. Close the User Account Manager by clicking x. TIP Services Users entered in authentication lists of FTP, web, or file server configurations are removed when user accounts are deleted.
Chapter 4 Windows CE Operating System The Server Config applet in the control panel configures settings used for VNC, web, FTP, file server, and KEPServer activities on an Ethernet network. Network Server Configuration VNC Server Configuration The VNC Server tab in the Network Server Configuration dialog box configures settings used by a client device to view or control the terminal over a VNC connection. The VNC service supports two concurrent client connections.
Windows CE Operating System Chapter 4 VNC Connection Requiring Password for View-only Operations The default VNC configuration enables view-only access to the terminal without requiring a password. This applies to the VNC viewer that resides on the terminal and the viewer you can deploy to a computer. This example uses the VNC viewer deployed to a computer to connect to the HMI terminal. TIP Copy vncviewer.exe, in the \Windows folder on the terminal, to your computer and install the TightVNC software.
Chapter 4 Windows CE Operating System VNC Connection with Separate Passwords for View and Control Operations You can configure the VNC server to require separate passwords for view-only and control operations. This example uses the VNC viewer deployed to a computer to connect to the HMI terminal. TIP Copy vncviewer.exe, in the \Windows folder on the terminal, to your computer and install the TightVNC software.
Windows CE Operating System Chapter 4 3. Clear View only (inputs ignored). 4. Click OK. 5. Enter the IP address of your terminal and click Connect. Click the network connection icon in the system tray to view IP information. The Standard VNC Authentication dialog box opens. 6. Enter the control password that was defined in the VNC configuration dialog box on the terminal and click OK. The PanelView VNC viewer opens. 7.
Chapter 4 Windows CE Operating System Web Server Configuration The Web Server tab in the Network Server Configuration dialog box configures settings that are used for HTTP web activities. These are standard Microsoft Windows CE parameters. TIP Always click OK to apply new settings. You are asked if you want to restart the service immediately. Table 54 - Web Server Parameters 108 Parameter Description Default Admin Users Specifies a list of users allowed to administer web activities.
Windows CE Operating System Chapter 4 FTP Server Configuration The FTP Server tab in the Network Server Configuration dialog box configures settings that are used for exchanging files over a network. These are standard Microsoft Windows CE parameters. The default FTP configuration lets any user establish an FTP connection to the HMI terminal by logging in anonymously and downloading files from the FTP default directory (\Temp). TIP Always click OK to apply new settings.
Chapter 4 Windows CE Operating System FTP Anonymous Login and Upload Follow these steps to establish an FTP connection to the terminal by allowing anonymous logins and file transfers to or from the default FTP folder on the terminal. TIP If Allow Anonymous Uploads is not checked, you can copy files from the default FTP folder on the terminal but not to the folder. 1. Open your web browser or any folder on your computer. You need the IP address of your HMI terminal to establish an FTP connection.
Windows CE Operating System Chapter 4 FTP Connection Requiring User Authentication Follow these steps to establish an FTP connection to the terminal by first entering a valid user name and password. 1. Open your web browser or any folder on your computer. 2. Type the IP address of the HMI terminal in the address field by using the syntax ftp://ipaddress_of_hmi_terminal. ftp://90.95.80.8 3. Click OK when you see the FTP Folder Error dialog box.
Chapter 4 Windows CE Operating System File Server Configuration The File Server tab in the Network Server Configuration dialog box provides settings that allow shared access to files, printers, serial ports, and miscellaneous communication between computers on a network. These are standard Microsoft Windows CE parameters. TIP Always click OK to apply new settings. You are asked if you want to restart the service immediately.
Windows CE Operating System Printer Support Chapter 4 The terminals supports selected USB printers such as Canon, Epson, HewlettPackard, and Brother. Automatic printer installation that uses plug-and-play capabilities is supported as well as manual installation if a suitable printer driver is available. You can connect a printer to a USB port on the terminal. For more information on supported printers, go to the knowledgebase at http:// www.rockwellautomation.
Chapter 4 Windows CE Operating System 3. Verify printer installation from the desktop control panel by opening the Printers applet. Notice the icon for the Deskjet 5650C printer. The check mark indicates this is the default printer. 4. From the File menu, choose Properties to view the properties of the printer. Printer configuration includes the printer name, manufacturer and model, printer driver, and port-specific parameters. • New printer configurations are retained through a power cycle.
Windows CE Operating System Chapter 4 Manual Printer Installation Follow these steps to manually set up a supported printer. 1. Connect the printer to the USB port. 2. Plug the power cord of the printer into an outlet and turn the printer on. 3. From the desktop control panel, open Printers. 4. Click Add Local Printer. 5. Follow the Add Local Printer Wizard instructions to configure the printer: a. Verify the connected printer appears on the USB printer port. b.
Chapter 4 Windows CE Operating System A PDF reader is available on all PanelView Plus 6 terminals and provides typical PDF view and search functions. You can run this reader from the Windows desktop or from a command prompt. PDF Reader When viewing a PDF document, you can initiate functions from the menu or toolbar. Bookmarks created in the original PDF appear under Bookmarks.
Windows CE Operating System Chapter 4 Command Prompt Parameters You can run the PDF reader from the Windows Command Prompt by choosing Start>Programs>Command Prompt and executing the command parameters in Table 59. Command Prompt Syntax Foxitreader “file_path/file-name.pdf ” parameter parameter_ value • Enclose the file path and file name in double quotes and use forward slashes to separate the file path directories and file name.
Chapter 4 Windows CE Operating System Notes: 118 Rockwell Automation Publication 2711P-UM006C-EN-P - April 2013
Chapter 5 Install and Replace Components Topic Page Install or Replace the Logic Module 120 Install or Replace a Communication Module 121 Replace the Display Module 123 Replace the Bezel 124 Replace the Backlight 126 Replace the Battery 130 Install the AC Power Supply Module 132 Remove the Product ID Label 134 Replace the Keypad Legend Inserts 134 Load an SD Card 135 Clean the Display 136 ATTENTION: Prevent Electrostatic Discharge This equipment is sensitive to electrostatic disch
Chapter 5 Install and Replace Components Install or Replace the Logic Module The display modules and logic modules for the 700, 1000, 1250, and 1500 terminals can be ordered as separate components for field installation. If modules are ordered as separate components, attach the logic module to the display module before panel installation. 1. Make sure power is disconnected from the terminal. 2. Set the display module display-side down on a clean, flat, stable surface. 3.
Install and Replace Components Chapter 5 4. Remove the four screws that secure the communication module, if attached, to the logic module and set the communication module aside. Communication Module Screw Logic Module Captive Screw Display Module 5. Loosen the four captive screws that secure the logic module to the display module. 6. Carefully lift the logic module from the back of the display.
Chapter 5 Install and Replace Components 2. If the display module is removed from the panel, set the terminal, displayside down, on a clean, flat, stable surface. COMM FAULT T DEFAUL RESET Connector for Communication Module 3. Position the communication module over the logic module so that the connector on the bottom of the module aligns with the connector on the logic module. 4. To prevent ESD between the modules, let the communication module touch the logic module before making the connection.
Install and Replace Components Chapter 5 Follow these steps to replace a communication module. 1. Disconnect power from the terminal. 2. Disconnect communication cables from the module. WARNING: Do not connect or disconnect any communication cable with power applied to this device or any device on a network. An electrical arc could cause an explosion in hazardous location installations. Be sure power is removed or the area is known to be nonhazardous before proceeding. 3.
Chapter 5 Install and Replace Components 7. Position the logic module over the new display module so that the connectors align. 8. Push down on the logic module until firmly seated. 9. Tighten the four captive secures that secure the logic module to the display module and torque to 0.58 N•m (5…7 lb•in). 10. Attach the communication module, if necessary, and torque the four screws to 0.58 N•m (5…7 lb•in). Replace the Bezel You can replace the bezel on the 700, 1000, 1250, and 1500 terminals.
Install and Replace Components Chapter 5 4. Disconnect the touch screen connector. Plate Touch Screen Connector 5. Remove the screws from the back of the display module. The number of screws varies for each terminal type. Display Module Bezel 6. Remove the sealing gasket. 7. Lift the back of the display module away from the bezel. Work on a clean, flat, stable surface to protect the display from debris, scratches and damage. 8. Detach the connectors.
Chapter 5 Install and Replace Components Replace the Display Module Bezel Follow these steps to replace the display module bezel. 1. Make sure the bezel is free of lint and marks before attaching. 2. Attach the connectors. • Function key connector • Connector on keypad or keypad/touch units 3. Place the back of the display module over the bezel. Be careful not to pinch any of the cables. Let the touch screen connector out of the access opening. 4. Attach the touch screen connector. 5.
Install and Replace Components Chapter 5 Follow these steps to replace the backlight. 1. Disconnect power from the terminal. 2. Remove the display module bezel. IMPORTANT The 700 series C display is not secured by screws and is retained only by a bracket. Use care not to drop the display once the bezel is removed. 3. Remove the four screws that secure the LCD display. For 700 displays, remove the four screws that secure the display bracket. 4.
Chapter 5 Install and Replace Components 6. Follow these steps for the 700 and 1000 displays. a. Press the retaining tab that secures the backlight, then pull out the backlight. Backlight Retaining Tab b. Insert the new backlight. Backlight 7. Follow these steps for the 1250 and 1500 displays. a. Remove the screws that secure the backlights and remove the backlights. For the 1250 series A and B displays, the two backlights are each secured with two screws.
Install and Replace Components Chapter 5 For the 1500 series B displays, remove the tape, then remove the backlights. 1250 Backlights 1500 b. Insert the new backlights then secure each with the same screws from the previous step, and torque to 0.117 N•m (1.04 lb•in). 8. Attach the LCD display connector to the circuit board. Refer to step 4. 9. Attach the backlight connector to the circuit board. Refer to step 5. 10. Secure the LCD display. a.
Chapter 5 Install and Replace Components Replace the Battery The product has a lithium battery that is used by the real-time clock. It is not used for backup or retention. This product contains a sealed lithium battery which may need to be replaced during the life of the product. At the end of its life, the battery contained in this product should be collected separately from any unsorted municipal waste.
Install and Replace Components Chapter 5 3. Lift up on the cover. 4. Remove the battery. CR2032 5. Insert the new battery with the positive (+) polarity facing up and press gently until the battery snaps into place. 6. Close the battery cover and push the end in until you hear a click. 700 to 1500 Terminals Follow these steps to replace the battery. 1. Disconnect power from the terminal. 2. Place the terminal, display side down, on a flat stable surface. 3.
Chapter 5 Install and Replace Components 5. Carefully lift the logic module away from the terminal and turn over to expose the circuit board. 6. Locate the battery on the circuit board. 7. Remove the battery by lifting up the side of the battery. The battery can be removed up to 15 seconds without losing clock and calendar data. 8. Insert the new battery. 9. Reattach the logic module by aligning the two connectors on the bottom of the logic module with the connectors on the back of the display module.
Install and Replace Components Chapter 5 3. Plug the DC power terminal block connected to the AC power supply module into the terminal. 4. Insert the two short tabs on the AC module into the slots on the back of the terminal. 4 5 5. Push down on the module until the two long tabs snap into the slots on the opposite side of the terminal. Make sure the module is securely connected and that the power supply wires are not pinched between the module and the terminal. 6.
Chapter 5 Install and Replace Components Remove the Product ID Label You can replace the product ID label on the terminal with a custom label. 1. Remove the Allen-Bradley label by using your fingers or a tweezers. 2. Clean area with damp cloth and isopropyl alcohol. 3. Remove adhesive backing of new label and affix to the same location. Replace the Keypad Legend Inserts Legend strips are available as separate catalog numbers for keypad terminals, except for the 400 keypad terminals.
Install and Replace Components Chapter 5 700 to 1500 Terminals On the 700 to 1500 terminals, the F1-Fxx legend strips are accessible from the back of the unit. The K1-Kxx legend inserts are accessible when the display bezel is removed. Follow these steps to replace the K1-Kxx key legend inserts. 1. Remove power from the terminal. 2. Remove the display module bezel as described on page 124. 3. Pull the legend inserts out from the slots on the bezel. 4.
Chapter 5 Install and Replace Components Follow these steps to install an SD card in the card slot. 1. Verify that the SD card is locked or unlocked according to your preference: • If unlocked, the terminal can write data to or read data from the card. • If locked, the terminal can only read data from the card. Unlocked Locked ATTENTION: Orient the SD card correctly before inserting into slot. Forcing the card into the slot can damage the card or the terminal. 2.
Chapter 6 Terminal Connections s Topic Page USB Ports 138 Ethernet Connections 140 Serial Connections 142 DH-485/DH+ Communication Module 145 ControlNet Communication Module 148 Controller Connections 151 ATTENTION: Wiring and Safety Guidelines Use publication NFPA 70E, Electrical Safety Requirements for Employee Workplaces, IEC 60364 Electrical Installations in Buildings, or other applicable wiring safety requirements for the country of installation when wiring the devices.
Chapter 6 Terminal Connections USB Ports The terminals have one or two USB 2.0 host ports and one USB 2.0 device port. Figure 14 - USB Ports 400 or 600 Terminal 700 to 1500 Terminal Mini USB Device Port USB Host Ports IMPORTANT USB Host Port USB Device Port The USB host and device ports are intended only for temporary use and must not be used for runtime operations.
Terminal Connections Chapter 6 The USB ports are identified by a USB icon. Each USB host port supports 0.5 A at 5V DC. Connected USB devices must not exceed this power load. Table 62 - USB Connector Pinouts USB Icon USB Ports Pin Signal Description 1 VCC +5V 2 D- Data - 3 D+ Data + 4 GND Ground 1 VCC +5V 2 D- Data - 3 D+ Data + 4 ID Distinguishes host connection from slave connection: • host: connected to Signal ground • slave: not connected 5 GND Ground Hi-speed USB 2.
Chapter 6 Terminal Connections Ethernet Connections The Ethernet port connects to a controller on an EtherNet/IP network by using standard Ethernet and network connections. The port also supports application transfers, and printing. The 2711P-RN20 Ethernet communication module is available for the 700 to 1500 terminals if another Ethernet port is required. The module has its own unique IP address.
Terminal Connections Chapter 6 The maximum cable length between the Ethernet port and a 10/100Base-T port on an Ethernet hub (without repeaters or fiber) is 100 m (328 ft). WARNING: Do not connect or disconnect any communication cable with power applied to this device or any device on the network. An electrical arc could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Chapter 6 Terminal Connections Serial Connections The RS-232 serial port is multi-purpose and supports these connections: • DH-485 communication through a serial connection • DF1 full-duplex communication with controllers by using direct connections or modem connections • Third-party point-to-point communication • Application transfers and printing The serial port is a 9-pin, male, RS-232 connector. Table 66 shows the pinout descriptions and how these pins map to the serial ports on the controllers.
Terminal Connections Chapter 6 Modem Connection Wire or radio modem communication is possible between the terminal and controller. Each modem must support full duplex communication. Refer to your modem user manual for details on settings and configuration. Figure 17 - Modem Connection PanelView Plus 6 Terminal Optical Isolator DF1 Port Controller Modem Modem Construct a Null Modem Cable To construct a null modem cable, refer to this pinout.
Chapter 6 Terminal Connections Computer Connections The RS-232 serial port supports application uploads and downloads between the terminal and a computer by using a direct connection. Figure 18 - Serial Port Connection to Computer Computer Cables Cat. No. 2711-NC13, 5 m (16.4 ft) Cat. No. 2711-NC14, 10 m (32.7 ft) Cat. No.
Terminal Connections DH-485/DH+ Communication Module Chapter 6 700 to 1500 terminals with a catalog number 2711P-RN6 or 2711P-RN6K communication module support communication with these networks: • DH+ networks • DH-485 networks The communication module has a separate port for each communication protocol. You can communicate with one network only at one time. Figure 19 - DH-485/DH+ Communication Module Connectors Allen Bradley DH-485 1 2 3 4 5 6 DH+ 2 1. Earth/Ground 2. Shield/Drain 3. Signal Ground 4.
Chapter 6 Terminal Connections DH-485 Network Port Wiring Refer to the figures to attach the RS-485 connector to a Belden 3106A or 9842 cable. Refer to Controller Connections on page 151 if you are using standard Allen-Bradley® cables. IMPORTANT A daisy-chained network is recommended. We do not recommend a hybrid star/daisy chain networks as shown.
Terminal Connections Chapter 6 DH+ Network Connections Use a Belden 9463 twin-axial or equivalent cable, catalog number 1770-CD, to connect a terminal to a DH+ link. You can connect a DH+ link in two ways: • Trunk line/drop line - from the drop line to the connector screw terminals on the DH+ connectors of the processor. • Daisy chain - to the connector screw terminals on the DH+ connectors on the processor.
Chapter 6 Terminal Connections ControlNet Communication Module 700 to 1500 terminals with a catalog number 2711P-RN15S or 2711P-RN15SK communication module support ControlNet communication and the transfer of applications between devices on a ControlNet network.
Terminal Connections Chapter 6 Software and Firmware Requirements The software and firmware must be installed on the development computer and the PanelView Plus 6 terminal to configure and communicate with an Allen-Bradley controller on a ControlNet network. Table 72 - ControlNet Unscheduled Communication Software/Firmware Minimum Version FactoryTalk View Studio 6.0 or later FactoryTalk View Machine Edition Runtime 6.
Chapter 6 Terminal Connections ControlNet Module Connectors Figure 24 - Cat. No.
Terminal Connections Controller Connections Chapter 6 The tables provide a summary of PanelView Plus 6 connections to controllers and interface modules for runtime communication.
Chapter 6 Terminal Connections Table 76 - PanelView Plus 6 Terminals to Logix Controllers Protocol PanelView Plus 6 Comm Port ControlLogix CH0 (9-pin RS-232) (DF1) CompactLogix CH0 (9-pin RS-232) (DF1 or DH-485) DF1 RS-232 (DF1) port (9-pin) All terminals 2711-NC13 (5 m/16 ft) 2711-NC14 (10 m/32 ft) 2706-NC13 (3 m/10 ft) 2711-NC13 (5 m/16 ft) 2711-NC14 (10 m/32 ft) 2706-NC13 (3 m/10 ft) — 2711-NC13 (5 m/16 ft) 2711-NC14 (10 m/32 ft) 2706-NC13 (3 m/10 ft) RS-232 (DH-485) port (9-pin) All terminal
Chapter 7 Firmware Upgrades Terminal Firmware Topic Page Terminal Firmware 153 Download Firmware Files 154 Firmware Upgrade Wizard 154 Upgrading Terminal Firmware from a Storage Device 155 Upgrade Terminal Firmware over the Network 158 Firmware components are packaged as execute-in-place (XIP) regions in a single System Code (SC) .img file. When the SC .
Chapter 7 Firmware Upgrades Download Firmware Files Download the appropriate firmware installation package from the Rockwell Automation website. The package is named: PVP6__6.x-yyyymmdd.exe, where: • is 400-600 or 700-1500 • 6.
Firmware Upgrades Chapter 7 You can run the FUW from within FactoryTalk View Studio software or from the Programs menu on your computer: • In FactoryTalk View Studio software, from the Tools menu, choose Firmware Upgrade Wizard. • Choose Start>Programs>Rockwell Software>FactoryTalk View>Tools>ME Firmware Upgrade Wizard. Upgrading Terminal Firmware from a Storage Device Upgrading firmware from a storage device is a two-step process.
Chapter 7 Firmware Upgrades 4. Follow these steps from this dialog box. a. Browse to the location of the firmware source files on your computer, where the FUP was installed. b. Choose the firmware revision for the upgrade. c. Click Next. It can take several seconds for the next dialog box to appear while the FUP is being retrieved. 5. From this dialog box, optionally select the KEPServer drivers you want included with the firmware, then click Next.
Firmware Upgrades Chapter 7 Upgrade Terminal Firmware by Using Firmware Upgrade Card Follows these steps to transfer firmware files from the USB flash drive or SD card to the terminal. This is the firmware upgrade card created in the previous section. IMPORTANT • Do not remove or accidently disconnect the USB flash drive or SD card while a firmware upgrade is in process. This could corrupt the firmware and make the terminal unstable. • Do not power off the terminal during a firmware upgrade.
Chapter 7 Firmware Upgrades You can upgrade firmware in a terminal connected to a computer over a direct network connection. The network connection requires a computer running the Firmware Upgrade Wizard (FUW) and RSLinx Enterprise software, version 5.0 or later. Upgrade Terminal Firmware over the Network RSLinx Enterprise software is required so that you can select the terminal on the network.
Firmware Upgrades Chapter 7 5. Navigate to and select the terminal to receive the firmware update, then click Next. 6. Follow these steps from this dialog box. a. Browse to the location of the firmware source files on your computer, where the FUP was installed. The default location is shown. b. Choose the version of the upgrade firmware from the pull-down menu. c. Click Next. It can take several seconds for the next dialog box to appear while the FUP is being retrieved. 7.
Chapter 7 Firmware Upgrades The final dialog box summarizes your choices for upgrading the terminal firmware. 8. Click Finish to update the firmware in the terminal. 9. Click Yes to continue with the update. A progress bar updates as firmware files are copied to the terminal. 10. Click OK when the firmware upgrade is complete. The terminal restarts, executing the new firmware.
Chapter 8 Troubleshooting Topic Page Status Indicators 161 Terminal Does Not Start Properly 162 Start-up Messages and Codes 164 Check Terminal Components 166 Ethernet Connection 167 Program Launcher ActiveX Control 168 Application Does Not Run 168 Configuration Mode Access 168 File System Errors 169 Advanced Diagnostics 169 Access Maintenance Operations 170 Restore Factory Defaults 172 The terminals have two status indicators to isolate operating anomalies: • COMM indicator (gre
Chapter 8 Troubleshooting Terminal Does Not Start Properly This section provides general troubleshooting information to assist you when trying to isolate anomalies. Check for Adequate Power A terminal that does not receive adequate power could result in unpredictable behavior. Refer to Chapter 2 for power requirements. Check Indicators at Startup When the terminal starts, the fault and comm indicators flash on and off, then the comm indicator flashes to signal progress during startup.
Troubleshooting Chapter 8 Check the Start-up Messages and Codes Refer to Start-up Messages and Codes on page 164 for a list of message states and error codes that can appear on the splash screen during startup. Check Voltages and Temperatures Check the battery voltage, processor temperature, and display temperature. Table 79 - Checking Voltage and Temperature Conditions Check for These Conditions Where What to Do Battery voltage < 2.
Chapter 8 Troubleshooting Start-up Messages and Codes The splash screen reports actions and status conditions that occur during startup. This includes firmware and hardware revision information. Figure 26 - Start-up Splash Screen Status or Error Code State Message © 2013 Rockwell Automation, Inc. All Rights Reserved. Logic Module Hardware Revision INIT Progress Bar N3 Boot Loader Firmware Revision RSLinx Enterprise Firmware Revision BL 02.12 01 OSEX OS 02.14 APP 01.03 APPEX 02.10 COMM 05.
Troubleshooting Chapter 8 Table 80 - Start-up Messages and Codes State Message Description State Message Code Recommended Action Load firmware image into RAM Update 1E Write firmware image to storage Update A5 Messages during firmware installation and loading are for information purposes only.
Chapter 8 Troubleshooting This section provides tips on how to isolate anomalies with the display, touch screen, keypad, attached keyboard, or mouse. If you are unable to resolve the anomaly, replace the touch screen display module (700-1500) or the terminal (400-600). Check Terminal Components Table 81 - Resolve Anomalies with Touch Screen Symptom Recommended Action The display does not have a touch screen. Check the catalog number of the unit.
Troubleshooting Chapter 8 Table 84 - Resolve Anomalies with Keyboard Symptom Recommended Action The keyboard is not operating correctly. Check the USB cable and connector. Detach and reattach the keyboard. Verify a good connection. Cycle power to the terminal. The keyboard is not accepting key input. Check key input by using the keypad: • If the keypad works, but the keyboard does not, then the keyboard driver or keyboard is not working.
Chapter 8 Troubleshooting Program Launcher ActiveX Control If desktop access is restricted and you use the Program Launcher - ActiveX control to launch a file viewer, text editor, or PDF reader, the system locks up when you try to open a file. To avoid this issue, associate a file with the application you are launching. The viewer, editor, or PDF reader automatically launches with the associated file.
Troubleshooting File System Errors Chapter 8 File system errors are rare as the internal file system is transaction safe. Always stop applications before removing power so that data is cleanly flushed out to the file system and the file system is brought to an orderly stop. Do not remove the external USB or SD storage devices while writing to the device is in progress.
Chapter 8 Troubleshooting Access Maintenance Operations The terminal typically launches the Windows desktop or a FactoryTalk View ME application on startup. You can also start the system in Maintenance mode for diagnostic and repair purposes. Table 86 - Maintenance Start-up Operations Operation Description None Exits Maintenance mode and continues with a normal restart. Safe mode Starts the system in Safe operating mode.
Troubleshooting Chapter 8 Access Maintenance Operations Follow these steps to access Maintenance actions at startup. Terminals require an attached USB keyboard to navigate in Maintenance mode. TIP 1. Insert a thin, nonconductive probe into the hole marked Default on the back of the logic module and press the switch. COMM FAULT DEFAULT RESET COMM FAULT LT DEFAU RESET To access this menu from a fault state, press the Reset switch, then press and hold the Default switch until you see the menu.
Chapter 8 Troubleshooting 2. Press the up and down arrow keys on the keypad or attached keyboard to move up and down the list of maintenance options: • Continue booting with selection option. • Special Boot Action • Display Resolution (not on 400 and 600 terminals) 3. With an option selected, press the right or left arrow keys to cycle through the available operations or settings. The result of each action is explained on the right.
Troubleshooting Chapter 8 After releasing the Reset switch, release the Default switch to enter the maintenance menu. Initial Maintenance Window default button pressed, please select maintenance options Maintenance Menu -- ver 0x.xx Continue booting with selected options Continue with this system boot Special BOOT Action - None This option will continue booting with the options selected on the left.
Chapter 8 Troubleshooting Notes: 174 Rockwell Automation Publication 2711P-UM006C-EN-P - April 2013
Appendix A Fonts Resident on Terminal True Type Fonts The table lists true type fonts that are pre-installed on the terminals. The default system font is Tahoma. TIP The Arial Unicode MS font contains almost 50,000 characters and provides default language support for many non-Latin languages and scripts including Arabic, Hebrew, Vietnamese, Thai, Hindi (Devanagari), and other Indic languages. The font also includes Chinese, Japanese, and Korean (CJK) support.
Appendix A Fonts Resident on Terminal Table 87 - True Type Fonts True Type Fonts File Name Microsoft Logo mslogo.ttf Symbol symbol.ttf Tahoma Tahoma (Subset 1_07) tahoma_1_07.ttf Tahoma Bold tahomabd.ttf Times New Roman Times New Roman (Subset 1_30) times_1_30.ttf Times New Roman Bold timesbd.ttf Times New Roman Bold Italic timesbi.ttf Times New Roman Italic timesi.ttf Trebuchet MS Trebuchet MS trebuc.ttf Trebuchet MS Bold trebucbd.ttf Trebuchet MS Bold Italic trebucbi.
Appendix B Outdoor Installations for High-bright Displays Important Considerations When using a high-bright display module outdoors, catalog number 2711P-RDT12H, there are important considerations in maximizing the field-life of the front bezel and display: • Using an antiglare overlay and visor • Selecting the proper enclosure • Using the proper orientation of the terminal Ultraviolet and infrared radiation can reduce the field life of any electronic device.
Appendix B Outdoor Installations for High-bright Displays Selecting an Enclosure The paint, color, size, and power dissipated by the internal components of an enclosure affect the temperature rise inside the cabinet. Hoffman, a Rockwell Automation Encompass Partner, has information to help you select an enclosure, and heating/cooling accessories to meet the temperature requirements of the installed equipment. See http://www.hoffmanonline.com.
Index A AC power AC power supply module 132 connection 42 functional earth ground 41 protective earth 41 accessories adapter plates 26 antiglare overlays 24 backlights 24 battery 25 bezel replacements 25 communication modules 23 logic modules 23 mounting hardware 25 power supply and terminal blocks 25 SD cards 24 solar visor 24 ActiveX controls 12, 78 Program Launcher 168 adapter plates 26 advanced diagnostics 101 alarm display, enable or disable 78 antiglare overlays 24, 177 application checking integrity
Index D date and time 79 DC power connection 40 earth ground 39 external power supply 38 default switch 171 deleting files applications 64 font files 64 log files 64 desktop access disable 55 enable 54 factory default state 13 open versus closed 12 reset password 56 set password 56 device name 63 DH485 network connections 145 port connectors 145 status indicators 145 DHPlus network connections 147 port connectors 145 status indicators 145 diagnostics in FactoryTalk View ME 75 dimensions panel cutout 30 pro
Index H hazardous location 28 high-bright displays antiglare overlay 177 installation 177 solar visor 177 I IGMP Protocol 141 input devices control panel 95 FactoryTalk View ME 69 mouse 69, 71 input panel 47 installation backlight 126 battery 130 bezel 124 environment and enclosure 27 hazardous location 28 high-bright displays 177 keypad legend inserts 134 mounting 700 to 1500 terminals terminal 35 panel cutouts 30 product dimensions 31 product label 134 USB peripheral devices 29, 138 Internet Group Manag
Index R regional settings FactoryTalk View ME 81-83 reset terminal 170 from maintenance window 170 reset switch 18, 43 restart system 43 restore factory defaults 170, 172 restore terminal image 90 right-click functionality on touch screen 86 RSLinx communication settings 58 run loaded application 50 runtime cables 151 S safe mode 100, 170 screen saver control panel 97 FactoryTalk View ME 68 SD card 24 loading 135 slot 135 using to back up and restore image 90 serial communication connections 142 DF1 142 D
Index U UPnP server 87 USB flash drive using to back up and restore image 91 USB ports connector pinouts 138 device port 14, 15, 18, 138 host ports 14, 15, 18, 29, 138 installation 29 user accounts 102 V VNC server 87 client viewers 86, 104 configuration 104 control and view connection example 106 control operations 104 security 104 view-only connection example 105 view-only operations 104 voltage battery 94, 163 W watchdog errors 101 web browser 12 web server 87 configuration 108 Windows CE operating sy
Index Notes: 184 Rockwell Automation Publication 2711P-UM006C-EN-P - April 2013
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support, you can find technical manuals, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. You can also visit our Knowledgebase at http://www.rockwellautomation.