Installation Instructions AC Power Supply for PanelView Plus/PanelView Plus CE Terminals Catalog Number 2711P-RSACDIN Topic Page Important User Information 2 Environment and Enclosure 3 Hazardous Locations 4 Overview 5 Install the Power Supply 6 Wire the Power Supply 7 Mounting Dimensions 8 Diagnostic Indicator 9 Specifications 9 Additional Resources 11 Publication 2711P-IN005C-EN-P - March 2007
AC Power Supply for PanelView Plus/PanelView Plus CE Terminals Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.
AC Power Supply for PanelView Plus/PanelView Plus CE Terminals 3 Environment and Enclosure ATTENTION Environment and Enclosure This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11.
AC Power Supply for PanelView Plus/PanelView Plus CE Terminals Hazardous Locations The following information applies when operating this equipment in hazardous locations: Products are suitable for use in Class 1, Div 2 Groups A, B, C, and D Hazardous Locations and nonhazardous location only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code.
AC Power Supply for PanelView Plus/PanelView Plus CE Terminals 5 Overview 1 2 PanelView Plus POWER 3 4 24 VDC POWER SUPPLY 2711P-RSACDIN 7 5 6 Item Description 1 Power Supply module 2711P-RSACDIN 2 Indicator 3 120/230V ac ground 4 120/230V ac common L2/N connections 5 120/230V ac power L1 connections 6 +24V dc connections 7 24V common connections ATTENTION The 2711P-RSACDIN power supply provides sufficient 24V dc power to a single PanelView Plus or PanelView Plus CE.
AC Power Supply for PanelView Plus/PanelView Plus CE Terminals Install the Power Supply WARNING If you connect or disconnect wiring while the field side power is on, an electrical arc can occur. This could cause an explosion in hazardous installations. Be sure that power is removed or the area is nonhazardous before proceeding. A B POWER 24 VDC POWER SUPPLY 2711P-RSACDIN PanelView Plus POWER 24 VDC POWER SUPPLY 2711P-RSACDIN C C 1. Position the power supply module A on a 35 x 7.
AC Power Supply for PanelView Plus/PanelView Plus CE Terminals 7 Wire the Power Supply PanelView Plus POWER 24V DC POWER SUPPLY 2711P-RSACDIN H (GR) A (L2/N) B COM (L1) C 24V J G FED IMPORTANT I Input and output wiring must be in accordance with Class I, Division 2 wiring methods per Article 501-4(b) of the National Electrical Code and in accordance with the authority having jurisdiction. Terminals A, B and C are 120/230V supply terminals.
AC Power Supply for PanelView Plus/PanelView Plus CE Terminals Mounting Dimensions Inches (Millimeters) PanelView Plus 2.0 (50) 3.2 (80) POWER 24V DC POWER SUPPLY 2711P-RSACDIN 3.4 (87) COM 1.2 (28) 24V 3.7 (94) 2711P-RSACDIN 3.4H x 3.7W x 2.
AC Power Supply for PanelView Plus/PanelView Plus CE Terminals 9 Diagnostic Indicator The power supply has one indicator. PanelView Plus POWER Power Indicator 24V DC POWER SUPPLY 2711P-RSACDIN COM 24V The power indicator is on (green) when voltage at the output is between 20.4 V dc and 28V dc. Indicator Description ON (green) Output voltage is greater than 20.4V dc, but less than 28V dc OFF No power applied to power supply.
AC Power Supply for PanelView Plus/PanelView Plus CE Terminals Output Current 3 A maximum horizontal mount Minimum Load 50 mA Overvoltage Protection Output internally limited to 35V dc. Cycle power to reenergize. Overcurrent Protection Current limit 3.2 A minimum (107% minimum) Leakage Current 0.5 mA rms maximum @ rated input and output Isolation Voltage 2830V dc for 1 second General Specifications Mounting Horizontal on a DIN rail.
AC Power Supply for PanelView Plus/PanelView Plus CE Terminals Conducted RF Immunity IEC 61000-4-6 10V rms with 1kHz sine wave 80% AM from 150 kHz to 80 MHz Emissions CISPR 11 Group 1, Class A (with appropriate enclosure) Enclosure Type Rating None (open-style) Power Conductors Wire Size 11 12 gauge (4 mm2) maximum solid or stranded copper wire rated at 75 °C or greater 3/64 in. (1.2 mm) insulation max.
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.