Hazardous Locations
This equipment is suitable for these locations:
Class I, Division 2 Groups A, B, C, D
Class I, Zone 2, Group IIC
Class II, Division 2 Groups F, G
Class III
Ordinary, nonhazardous locations only
The following statement applies to use in hazardous locations.
The terminals have a temperature code of T4 when operating in a 55 °C (131 °F)
maximum ambient temperature. Do not install the terminals in environments where
atmospheric gases have ignition temperatures less than 135 °C (275 °F).
WARNING
Explosion Hazard
Substitution of components may impair suitability for hazardous locations.
Do not disconnect equipment unless power has been switched off and area is known to
be nonhazardous.
Do not connect or disconnect components unless power has been switched off.
All wiring must comply with N.E.C. articles 501, 502, 503, and/or C.E.C. section 18-1J2
as appropriate.
Peripheral equipment must be suitable for the location in which it is used.