Reference Manual

73Numerics
Publication 2711E-820 – January 1998
20383
MOV
MOVE
SOURCE: N7:11
DEST: N7:12
Enter Bit
N7:10
] [
N7:10
] [
01
Rung for DH+ or ControlNet Application
To select the value to change, press the SELECT button on the
PanelView terminal to enable the Set Bit Cursor Point object.
Use the arrow keys to select the value, then press the Numeric
Keypad Enable Button and enter the new value.
Example 4: Numeric Input Cursor Point (for keypad terminals)
Numeric Input Cursor Point
Numeric Input Cursor Point objects change an array of values.
To select which value to change, press the SELECT button on
the PanelView terminal to enable the Numeric Input Cursor
Points and to open the scratchpad at the top of the screen. Use
the arrow keys to select the value to change, then use the
Numeric Keypad to enter the data in the window. Use the Enter
key to send the data to the PLC.