Reference Manual
136 Scrolling Lists
Publication 2711E-820 – January 1998
Create the Manual Mode Rung
Rung 2:4 places the process in Manual mode. It moves a 0 to the
Cursor Control Address and permits the Cursor List buttons to
control the cursor. This rung also places the currently “On” station to
“Stand-By” when Auto mode is switched to Manual.
23701
Rung 2:4
MANUAL
FROM PLC
B40
] [
0
CURSOR
CONTROL
ADDRESS
MANUAL
FROM PV
N30:3
] / [
1
AUTOMODE
B40
( U )
MOV
MOVE
Source
Dest
0
N30:10
0
1
MANUAL
ONE SHOT
B40
[ ONS ]
7
MOV
MOVE
Source
Dest
1
N33[N30:1]
1
EQU
EQUAL
Source A
Source B
N33[N30:1]
1
2