Quick Start Manual User Manual

Publication 2711-QS003D-EN-P - June 2009 51
Creating the Application Chapter 3
3. For each row, edit the attributes shown:
Double-click in the Message Text field and type the alarm
message.
Double-click in the Value/Bit (Bit offset) field and enter the
value shown.
Click the check box in the Ack field.
4. Click OK to exit the Alarms dialog.
Bit triggered alarm messages are defined by a bit offset (Value/Bit
field) from the Trigger Tag address. For example, if the Trigger Tag
address is defined as B3:1/0, alarm messages can be triggered from
addresses B3:1/1 and B3:1/2.
When the motor speed reaches 1200 rpm, the logic controller sets bit
B3:1/2, triggering an alarm condition. The message MOTOR SPEED
HIGH! will appear in the alarm banner.
When the motor speed reaches 1500 rpm, the logic controller sets bit
B3:1/1, triggering an alarm condition. The message MOTOR SPEED
HIGH HIGH! will appear in the alarm banner.
Edit these fields.
B3:1/0
+
2=
Trigger Tag Address
Value/Bit of Alarm Message
B3:1/2
Logic Controller Address
B3:1/0
+
1=
Trigger Tag Address
Value/Bit of Alarm Message
B3:1/1
Logic Controller Address