Instruction Manual
Troubleshooting
Appendix B
B-5
Problem What to doCause
While trying to download an application file, a
PROBLEM window appears stating: Error code
208 was returned by the PassThrough Utility".
The PassThrough Utility has been unable to
establish DH+ communications with the PLC5.
Make sure the Programming Terminal DH+
Address" and the PLC DH+ Address" are
properly assigned.
Make sure that you have selected the proper
DH+ Hardware Driver" for your system, and that
the DH+ Driver Card Location" code is correct.
Immediately after completing a PLC5
PassThrough Download, a Minor Fault Status
bit is set in the PLC5.
The rack assignment configuration of the
application file downloaded to the PanelView
1200 terminal did not exactly match the
application file that was overwritten.
Use the PLC5 6200 Series software to clear the
Minor Fault; then reconfigure the PLC5 to
recognize the new rack assignment.
PLC Controllers Required for PassThrough
Important Only specific models and revisions of PLC controllers are
capable of the Pass-Through download/upload. Refer to the following table
for compatible models and revisions.
Processor Series Revision Valid PLC Racks Baud Rates
PLC5/11
All All 3 octal 57.6 kbps
115.2 kbps
230.4 kbps
PLC5/15 B N or later 1-3 octal 57.6 kbps
PLC5/20 All All 13 octal 57.6 kbps
115.2 kbps
230.4 kbps
PLC5/25 A J or later 1-7 octal 57.6 kbps
PLC5/30 A B or later 1-7 octal 57.6 kbps
115.2 kbps
230.4 kbps
PLC5/40 A
B
E or later
B or later
1-17 octal 57.6 kbps
115.2 kbps
230.4 kbps
PLC5/60 A
B
E or later
B or later
1-27 octal 57.6 kbps
115.2 kbps
230.4 kbps
PLC5/250 All All 1-37 octal 57.6 kbps
115.2 kbps
230.4 kbps