Instruction Manual

Troubleshooting
Appendix B
B-5
Problem What to doCause
While trying to download an application file, a
PROBLEM window appears stating: Error code
208 was returned by the PassThrough Utility".
The PassThrough Utility has been unable to
establish DH+ communications with the PLC5.
Make sure the Programming Terminal DH+
Address" and the PLC DH+ Address" are
properly assigned.
Make sure that you have selected the proper
DH+ Hardware Driver" for your system, and that
the DH+ Driver Card Location" code is correct.
Immediately after completing a PLC5
PassThrough Download, a Minor Fault Status
bit is set in the PLC5.
The rack assignment configuration of the
application file downloaded to the PanelView
1200 terminal did not exactly match the
application file that was overwritten.
Use the PLC5 6200 Series software to clear the
Minor Fault; then reconfigure the PLC5 to
recognize the new rack assignment.
PLC Controllers Required for PassThrough
Important Only specific models and revisions of PLC controllers are
capable of the Pass-Through download/upload. Refer to the following table
for compatible models and revisions.
Processor Series Revision Valid PLC Racks Baud Rates
PLC5/11
All All 3 octal 57.6 kbps
115.2 kbps
230.4 kbps
PLC5/15 B N or later 1-3 octal 57.6 kbps
PLC5/20 All All 13 octal 57.6 kbps
115.2 kbps
230.4 kbps
PLC5/25 A J or later 1-7 octal 57.6 kbps
PLC5/30 A B or later 1-7 octal 57.6 kbps
115.2 kbps
230.4 kbps
PLC5/40 A
B
E or later
B or later
1-17 octal 57.6 kbps
115.2 kbps
230.4 kbps
PLC5/60 A
B
E or later
B or later
1-27 octal 57.6 kbps
115.2 kbps
230.4 kbps
PLC5/250 All All 1-37 octal 57.6 kbps
115.2 kbps
230.4 kbps