Instruction Manual

Installing Your PanelView 1200 Terminal
Chapter 3
3-11
Figure 1.12
Color
T
ouch Screen Terminal Dimensions
21191
0.680"
(17.27 mm)
13.50"
(342.90 mm)
13.80"
(350.52 mm)
0.520"
(13.21 mm)
15.305"
(388.75 mm)
0.400"
(10.16 mm)
12.40"
(314.96 mm)
PanelView
Color
Touch Screen
Installation Notes
PanelView 1200 terminals are installed in a rectangular cut-out in a panel.
Depending on the model, the terminals mount with mounting studs or
mounting clips.
With the stud-mount models (TA4, TC4, KA1, KC1) nuts are provided
with the terminal. A gasket is fixed on the faceplate. Tighten the terminal
down onto the enclosure to compress this gasket. The gasket has built-in
spacers that will not allow it to be over-compressed. You will notice that
the tightening torque increases significantly when you reach the correct
compression. At this point the tightening torque should not exceed 10
inch-pounds.
With the clip-mount touch screen terminals (TA1, TC1), four mounting
clips are provided. Assemble the mounting clips before installing the
terminal.
Use a screwdriver to install two clips on each side. (See Figure 1.16.)
Tighten the screws until the chassis is held snugly in place against the
panel. A torque of 10 inch-pounds provides a good seal. Do not
over-tighten the screws.
PanelView 1200 Terminal
Cutouts