Installation Instructions Owner's manual

Chapter 5
Installation
5–7
The following wire and cable length restrictions apply to DTAM products
that are CE marked when used in installations that require compliance to
European EMC Directive 89/336:
DC Power Wiring 10 meters
Ground Terminal Wire 3 meters
Communication Cables 30 meters
These restrictions apply to the following catalog numbers: 2707L8P1 Series
D, 2707L40P1 Series D and 2707V40P1 Series D.
2707M232P3 Series E and 2707M485P3 Series E
2707L8P1 Series D, 2707L40P1 Series D and 2707V40P1 Series D
The DTAM Plus accepts supply voltages in the following ranges depending
upon the power supply designation.
Versions with P1 power supply, accept 15-23V AC (47 to 440 Hz)
or 20-30V DC
Series D versions with P1 power supply only, accepts 20-30V DC
Versions with P2 power supply, accept 85-265V AC (47 to 440 Hz)
or110-300V DC
To connect the DTAM Plus to a power source:
!
ATTENTION: Verify that the power is disconnected from the
power source before wiring. Failure to disconnect power may
result in electrical shock.
Make sure that the supply voltage to the DTAM Plus is correct,
refer to the voltage label on back of unit. The incorrect voltage
may damage the DTAM Plus.
Do not overtighten the power connector screw terminals.
Overtightening the terminals may damage the DTAM Plus.
1. Make sure that the voltage source is not turned on.
2. Use AWG#16 or #14 stranded wire to connect the DTAM Plus screw
terminals to the power source (see below).
Note: The power supply terminal block on the DTAM Plus is not
removeable.
Wire and Cable Length
Restrictions
Connecting Power