The normal response to a function 03 query is to echo the address,
function code, starting address and the data for the registers that were
requested.
Response for Requesting Variable Data
Change the InView Display Address
This function allows the ability to change the serial address in a
display. For example change display address 001 to address 020.
When doing this, you need to know the address of the display you
want to change. This is typically done using the automation software.
The following is an example of changing a display (with the address
of 005) to address 004.
Transmission:
Transmission for Changing the Serial Address
Response: NONE
Beginning
of Frame
ADDR FUNC BYTE
COUNT
DATA
OUTPUT
REG H.O.
0002
DATA
OUTPUT
REG L.O.
0002
DATA
OUTPUT
REG H.O.
0003
DATA
OUTPUT
REG L.O.
0003
:140306002C003F
DATA
OUTPUT
REG
H.O.
0004
DATA
OUTPUT
REG L.O.
0004
LRC EOF Ready to
rec. resp
00 01 77 CR LF
Beg of
Frame
ADDR FUNC H.O.
ADDR
L.O.
ADDR
DATA EOF Ready to rec. resp
: 05 01 00 64 ^AZ05^BE704^DCRLF
TIP
See section InView Display Communication Protocol
Functions and Descriptions on for further
explanation of the InView sign protocol being used.