User Manual Manual

Publication 2706-UM016D-EN-P - March 2006
4-34 InView Protocol
information received. The following is an example of adding message
#0003 and removing message #0002 from the message queue.
Transmission:
Transmission for Add/Remove a Message
Response: NONE
Priority Messaging using a Modbus ASCII Query (Recommended)
This method writes to the first register in the message queue (40103).
When this happens, the previous message in the queue is replaced
with the new message to be loaded.
This is an example of sending a Priority Message #0099 to display
address 001.
Transmission:
Query for a Priority Message
Response:
The normal response to a function 06 is to echo (or re-transmit) the
query after the holding register is updated.
Beginning
of Frame
ADDR FUNC H.O.
ADDR
L.O.
ADDR
QUANTITY BYTE CNT DATA
: FF 10 00 64 0002 04 0003 0002
LRC
Error
EOF Ready
to rec.
resp
7E CR LF
Beginning
of Frame
ADDR FUNC H.O.
ADDR
L.O.
ADDR
DATA LRC
Error
EOF Ready to
rec. resp
: 01 06 00 66 0063 30 CR LF