Selecting the Operating Mode
The DL40 Plus Slave display operates in one of four modes. Chapter
1 briefly describes these modes. For detailed descriptions refer to the
individual chapters describing each mode. Select the mode using
position #1 and #2 of DIP Switch #1.
Display Language
The DL40 Plus Slave displays characters in one of three language
sets. Appendix B lists the characters in each of the language sets. Set
the display language using positions #3 and #4 of DIP Switch #1.
Baud Rate
Select the baud rate that matches the rate of the host device. Both the
RS-232 and RS-485 ports are set at this rate. Set the rate using
positions #5 and #6 of DIP Switch #1. The DL40 Plus Slave displays
the currently set baud rate during its powerup sequence.
12 345 6 7 8910
12 34567 8910
Mode (DL Slaves Setting)
DIP #1
DIP #2
↓ ↓
↓ ↑
↑ ↓
↑ ↑
12 34567 8910
12 34567 8910
Language (English Setting)
DIP #1
DIP #2
↓ ↓
↓ ↑
↑ ↓
↑ ↑
12 34567 8910
12 34567 8910
Baud Rate (9600 Setting)
DIP #1
DIP #2
↓ ↓
↓ ↑
↑ ↓
↑ ↑