8–14
Setting Serial Port
After setting parity, you are prompted for the RS-422 port.
USE 422 IN? N
The DL20 RS-422 port can transmit and receive data from other DL20
devices used as addressable masters or slave DL10 / DL50 displays.
If you want to use the port as an output, answer No. All data output at the
RS-232 port will also be transmitted at the RS-422 port. Set the port to
output if slave displays or addressable masters are being used.
If you want to use the port as an input, answer Yes. Data can then be
received at the RS-422 port just like the RS-232 port.
After selecting RS-422 port direction, you are prompted for a blank line
between messages.
PRINT BLANK LINE?
Answering No reduces the amount of paper used and answering Yes makes
the printout easier to read.
Serial Port Default Values
Table 8.A lists the default values for the serial port.
Table 8.A
Serial Port Defaults
Parameter Setting Options
Printer Carriage Width 80 Columns 20 - 220 Columns
Number of Nulls 4 0 - 250
Baud Rate 9600 300, 1200, 9600
Parity None None, Odd, Even
422 Port Direction Output Input or Output
Print Blank Line Yes Yes or No
Setting Up I/O