User Manual
2
Overview
The RediSTATION has one bicolor LED (red/green) to show its
operating status. The LED shows the following indications.
Color State Indication
None Off No power.
Solid Unrecoverable fault.
Red
Flashing
Output error or configuration error.
Green
Solid Normal runtime operation.
The RediSTATION device is operating as a slave to
the master controller.
Flashing Device is idle or not allocated to a master.
The LED is visible when the cover of the enclosure is removed.
The RediSTATION has one 10-position DIP switch for setting:
• DeviceNet Node Address
• DeviceNet Data Rate
• Output Fault State (Off or Last State)
• Output Flash Rate
The DIP switch is located on the circuit board inside the enclosure.
The switch settings and functions are shown below. The default
setting for each switch or group of switches is underlined.
Default Configuration
OFF = 0
ON = 1
Output Fault State 0 = Outputs Turn Off on Fault
1 = Outputs Hold Last State on Fault
DeviceNet Address 000000 – 111111
(0 to 63)
10 123456789
Output Flash Rate 0 = 1 Hz (0.5 sec On, 0.5 sec Off)
1 = 2 Hz (0.25 sec On, 0.25 sec Off)
DeviceNet Data Rate 00
= 125K BPS
01 = 250K BPS
10 = 500K BPS
11 = Invalid
LED Indicator
DIP Switches