Instruction Manual

Publication 520-IN012A-EN-P - July 2014
Installation Instructions
PowerFlex 520-Series EMC Cores
Catalog Numbers: 25-CORE-A, 25-CORE-B, 25-CORE-C, 25-CORE-D, 25-CORE-E, 25-CORE-RF-A, 25-CORE-RF-B, 25-CORE-RF-C,
25-CORE-RF-D, 25-CORE-RF-E
25-CORE-A...D
25-CORE-RF-A...D
IMPORTANT
EMC cores are included with:
drives that have an internal EMC filter (25x-xxxxN114)
external EMC filter accessory kit (25-RFxxx)
25-CORE-RF-E 25-CORE-E
EMC Core Requirements
Frame Size
Class C1 Class C2 Catalog
Number
Frame Size
Class C1 Class C2 Catalog
Number
Enclosure Conduit or
Shielded
Cable @ Input
EMC Cores
Required
Enclosure Conduit or
Shielded
Cable @ Input
EMC Cores
Required
Enclosure Conduit or
Shielded
Cable @ Input
EMC Cores
Required
Enclosure Conduit or
Shielded
Cable @ Input
EMC Cores
Required
100...120V AC (-15%, +10%) – 1-Phase Input with External EMC Filter, 0...120V 1-Phase Output 380...480V AC (-15%, +10%) – 3-Phase Input with External EMC Filter, 0...460V 3-Phase Output
ANoNoNoNoNoNoNo AYesYesNoNoNoInput/Output25-CORE-RF-A
BNoNoNoNoNoNoNo BYesYesNoNoNoInput/Output25-CORE-RF-B
200...240V AC (-15%, +10%) – 1-Phase Input with External EMC Filter, 0...230V 3-Phase Output C Yes Yes No No No Input only 25-CORE-RF-C
A Yes Yes No No No Input/Output 25-CORE-RF-A D Yes Yes Output only No No Input/Output 25-CORE-RF-D
B Yes Yes Output only No No Input/Output 25-CORE- RF- B E Ye s Yes No Yes No I np ut/ Ou tp ut 2 5- CO RE -E
200...240V AC (-15%, +10%) – 1-Phase Input with Internal EMC Filter, 0...230V 3-Phase Output
(1)
380...480V AC (-15%, +10%) – 3-Phase Input with Internal EMC Filter, 0...460V 3-Phase Output
(1)
A* * * Yes No No A* * * No No Input/Output25-CORE-A
B* * * Yes No No B* * * No No Input/Output25-CORE-B
200...240V AC (-15%, +10%) – 3-Phase Input with External EMC Filter, 0...230V 3-Phase Output C * * * No No Input/Output 25-CORE-C
A Yes Yes Output only No No Input/Output 25-CORE-RF-A D * * * No No Input/Output 25-CORE-D
B Yes Yes Output only No No Input/Output 25-CORE-RF-B E * * * No No Input/Output 25-CORE-E
C Yes Yes Output only No No Input/Output 25-CORE-RF-C 525...600V AC (-15%, +10%) – 3-Phase Input with External EMC Filter, 0...575V 3-Phase Output
D Yes Yes No No No Input only 25-CORE-RF-D A Yes Yes No No No Input/Output 25-CORE-RF-B
E Yes Yes Output only No No Input only 25-CORE-RF-E B Yes Yes No No No Input/Output 25-CORE-RF-B
C Yes Yes No No No Input/Output 25-CORE-RF-C
D Yes Yes No No No Input/Output 25-CORE-RF-D
(1) An (*) indicates that EMC requirements are not met. E Yes Yes No Yes No No
IMPORTANT
An enclosure, shielded input cable, and EMC cores
are not required to meet class C3 requiremets.
2
DC+ DC–
0V
0V
1
L1 L2 L3
O
I
Wait three minutes after shutdown for
capacitors to discharge to safe voltage levels.
For more information, see “Installation Requirements Related to EN 61800-3 and the EMC Directive” in the PowerFlex 520-series user manual, publication 520-UM001.
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
EMI ttings and metal conduit
IP 30/NEMA 1/UL Type 1
option kit or EMC kit
Shielded enclosure
(1)
Building structure steel
Enclosure ground connection
EMI lter
L1'
L2'
L3'
L1
L2
L3
Shielded motor cable
Esc
Sel
(1) Some installations require a shielded enclosure.
Keep wire length as short as possible between
the enclosure entry point and the EMI filter.

Summary of content (2 pages)