Rockwell Automation Publication 20P-UM001K-EN-P - July 2014 95
Drive Start Up Chapter 2
Verify the Control Voltages
Verify that the following voltages are present at I/O terminal block 1 and
2. See I/O Signal and Control Wiring on page 81
:
Load the Default Settings
It is recommended that you reset the drive to the default settings. By resetting the
drive to the default settings, any previous parameter modifications you have made
will be overwritten.
1. On the HIM, from the “Main” menu scroll to the “Memory Storage”
menu.
2. Press Enter.
3. Scroll to “Reset To Defaults” and press Enter.\
A message displays to verify that you want to reset the drive to the
factory settings.
4. Press Enter.
Note: A “Params Defaulted” (F48) entry will be made in the drive’s Fault
Queue to indicate the change.
Configure the Most Commonly Used Parameters
If your application only requires basic drive parameter set up, you can use the
S.M.A.R.T. list screen available on the HIM to program the drive. See Using the
S.M.A.R.T. List Screen on page 267
for more information.
Terminal Number Voltage to Terminal Number
7 +10V 9
8-10V 9
19 +24 - 30V 18
To access all parameters in this procedure you must set the Parameter View
option to “Advanced”.