Input/Output Connection Example Required Parameter Changes
Potentiometer Unipolar Speed
Reference
10kΩ Pot. Recommended
(2kΩ Minimum)
Adjust Scaling:
72 [Anlg In1 Scale] and
73 [Anlg1 Tune Scale]
View Signal Value:
1404 [Analog In1 Value]
View Signal Output:
385 [Speed Ref Out]
Note: Verify that DIP switch S9 is set
to “On” (0…10V). See Tab le 27
on
page 54.
Joystick Bipolar Speed
Reference
±10V Input
Important: See the Attention
statement on page 80
for important
bipolar wiring information.
Set Direction Mode:
1322 [Direction Mode]
= 1 “Bipolar”
Adjust Scaling:
72 [Anlg In1 Scale] and
73 [Anlg1 Tune Scale]
View Signal Value:
1404 [Analog In1 Value]
View Signal Output:
385 [Speed Ref Out]
Note: Verify that DIP switch S9 is set
to “On” (0…10V). See Tab le 27
on
page 54.
Analog Input Bipolar Speed
Reference
±10V Input
Important: See the Attention
statement on page 80 for important
bipolar wiring information.
Set Direction Mode:
1322 [Direction Mode]
= 1 “Bipolar”
Adjust Scaling:
72 [Anlg In1 Scale] and
73 [Anlg1 Tune Scale]
View Signal Value:
1404 [Analog In1 Value]
View Signal Output:
385 [Speed Ref Out]
Note: Verify that DIP switch S9 is set
to “On” (0…10V). See Tab le 27
on
page 54.
Analog Input Unipolar Speed
Reference
0…+10V Input
or
0…20 mA or 4…20 mA
Configure for Voltage or Current:
71 [Anlg In1 Config]
Adjust Scaling:
72 [Anlg In1 Scale] and
73 [Anlg1 Tune Scale]
View Signal Value:
1404 [Analog In1 Value]
View Signal Output:
385 [Speed Ref Out]
Note: Verify that DIP switch S9 is set
to “On” for 0…10V operation, or
“Off” for 0…20 mA or 4…20 mA
operation. See Table 27
on page 54.
1