Chapter 1 Installation and Wiring
Table 32 - Drives with 690V Input - DIP Switch S15 Configuration
I/O Wiring
Observe the following points when installing I/O wiring:
Use copper wire only.
Wire with an insulation rating of 600V or greater is recommended.
Frame Drive Current
Rating Code
S15-1 S15-2 S15-3 S15-4 S15-5 S15-6 S15-7 S15-8
C 452 OFF OFF OFF OFF OFF OFF ON ON
565 ON OFF OFF OFF OFF OFF ON ON
D 678 OFF ON OFF OFF OFF OFF ON ON
791 ON ON OFF OFF OFF OFF ON ON
904 ON OFF ON OFF OFF OFF ON ON
1K0 OFF ON ON OFF OFF OFF ON ON
1K1 ON ON ON OFF OFF OFF ON ON
1K2 OFF OFF OFF ON OFF OFF ON ON
1K4 OFF ON OFF ON OFF OFF ON ON
1K5 ON ON OFF ON OFF OFF ON ON
I/O terminals labeled “(–)” or “Common” are not referenced to earth ground
and are designed to greatly reduce common mode interference. Grounding
these terminals can cause signal noise.
ATTENTION: Configuring an analog input for current operation and driving it from
a voltage source could cause component damage. Verify proper switch
configuration prior to applying input signals. See DIP Switch and Jumper Settings
on page 75
.
ATTENTION: Hazard of personal injury or equipment damage exists when bipolar
input sources are used. Noise and drift in sensitive input circuits can cause
unpredictable changes in motor speed and direction. Use speed command
parameters to help reduce input source sensitivity.