User Manual

72 Rockwell Automation Publication 20P-UM001K-EN-P - July 2014
Chapter 1 Installation and Wiring
Table 23 - Frame D, Series B Heatsink Cooling Fan Terminal Designations
Table 24 - Frame D Heatsink Cooling Fan Signal Wire Sizes and Terminal Specifications
Figure 51 - Frame D Heatsink Cooling Fan Terminal Block Location
Terminal Block Terminal Description AC Voltage Max Current
U3 Three-phase AC input
power connections
400…460V AC
(50/60 Hz)
1.5 A
V3
W3
PE Safety ground
31 Normally closed contact 250V AC 1 A
32
Terminals Wire Size and Type
(1)
(1) See Cable and Wiring Recommendations on page 43 for more information.
Tightening Torque
Nm (lbin)
Flexible (mm
2
) Multi-core (mm
2
)AWG
U3, V3, W3, 31, 32, PE 0.14…1.5 0.14…2.5 28…12 0.5…0.6 (4.4…5.3)
U3 V3 W3 PE 31 32
U3 V3 W3 PE 31 32
Top View
of Drive
Series B terminal
block shown