Diagnostics Menu
When a fault trips the drive, use this menu to access detailed data about the drive.
Parameter Menu
Use this menu to view and edit parameters for the drive. When you enter the the
Parameter menu, by default the
File–Group–Parameter view is displayed. To access
other views for the Parameter menu, with "Parameter" highlighted in the Main
menu, press Alt then Sel (View), select the desired view in the list and press
Enter. The following selections are available:
See Viewing and Editing Parameters on page 270
for more information.
Device Select Menu
Use this menu to access parameters in connected peripheral devices.
Memory Storage Menu
Drive data can be saved to, or recalled from, HIM sets.
HIM sets are files stored in permanent nonvolatile HIM memory.
Option Description
Faults View fault queue or fault information, clear faults or reset drive.
Status Info View parameters that display status information about the drive.
Device Items View statistics associated with DPI Communication.
Device Version View the firmware version and hardware series of components.
Option Description
Param Access Lvl Displays parameter 211 [Param Access Level]. The PowerFlex DC drive is initially set to the
Basic Parameter view. To view all parameters, set parameter 211 [Param Access Lvl] to
option 1 “Advanced”.
File-Group-Par (FGP) Displays all parameters in a File - Group - Parameter structure. This simplifies programming
by grouping parameters that are used for similar functions.
Numbered List Displays all parameters in numerical order.
Changed Params Displays the most recently changed parameter. You can scroll through the list of all changed
parameters to the least recently changed. The new and default values are listed for each
parameter.
ATTENTION: It is recommended that you stop the drive before performing a
download to the drive using the HIM CopyCat function, DriveExecutive™, or
DriveExplorer™.
Option Description
HIM CopyCat
Device -> HIM Save data to a HIM set.
Device <- HIM Load data from a HIM set to active drive memory.
Delete HIM Set Delete a HIM set.
Reset To Defaults Restore the drive to its factory default settings.