User Manual
258 Rockwell Automation Publication 20P-UM001K-EN-P - July 2014
Appendix A Supplemental Drive Information
Dynamic Brake Resistor Kits
and DC Output Contactors
See Table 82 and Tab l e 8 3 on page 260 for recommended alternate DC Output
Contactors for 575V and 690V AC input drives, respectively.
Table 80 - 230V AC Input Drives
Table 81 - 460V AC Input Drives
Frame
Drive Current
Rating Code
DC
Amps
AC Line
Amps
Hp Dynamic Brake
Resistor Kit Cat. No.
Armature
Voltage
(Volts)
Total DB
Resistance
(ohms)
DC Loop Contactor Cat. No.
(2)
DC Contactor
Crimp Lugs
Cat. No.
(3)
Drive without Dynamic
Brake
Drive with Dynamic
Brake
A 7P0 7 5.7 1.5 1370-DBL62 240 20 1370-NC56 1370-DC56 1370-LG40
9P0 9 7.4 2 1370-DBL63 240 20 1370-NC56 1370-DC56 1370-LG40
012 12 9.8 3 1370-DBL64 240 15 1370-NC56 1370-DC56 1370-LG40
020 20 16 5 1370-DBL65 240 8.6 1370-NC56 1370-DC56 1370-LG40
029 29 24 7.5 1370-DBL66 240 6 1370-NC56 1370-DC56 1370-LG40
038 38 31 10 1370-DBL67 240 5 1370-NC56 1370-DC56 1370-LG40
055 55 45 15 1370-DBL68 240 3.5 1370-NC56 1370-DC56 1370-LG56
073 73 60 20 1370-DBL69 240 2.6 1370-NC110 1370-DC110 1370-LG92
093 93 76 25 1370-DBL70 240 2 1370-NC110 1370-DC110 1370-LG92
110 110 90 30 1370-DBL71 240 2 1370-NC110 1370-DC110 1370-LG110
B 146 146 119 40 1370-DBL72 240 1.4 1370-NC180 1370-DC180 1370-LG160
180 180 147 50 1370-DBL73 240 1.0 1370-NC180 1370-DC180 1370-LG180
218 218 178 60 1370-DBL74 240 1.0 1370-NC280 1370-DC280 1370-LG228
265 265 217 75 1370-DBL75 240 0.67 1370-NC280 1370-DC280 1370-LG268
360 360 294 100 1370-DBL76 240 0.47 ABB_EHDB360C2P-1L2S ABB_EHDB360C-1L22SS
(4)
434 434 355 125 CUTLER-
HAMMER_G3AP50
(Qty 4 - two in series,
two in parallel)
240 0.4 ABB_EHDB520C2P-1L2S ABB_EHDB520C-1L22SS
(4)
C 521 521 426 150 HUBBELL_Y139W322
GB
240 0.322
(4)
700 700 572 200
(1)
240 0.25 ABB_EHDB800C2P-1L2S ABB_EHDB800C-1L22SS
(4)
D 875 875 715 250
(1)
240 0.2 ABB_EHDB960C2P-1L2S ABB_EHDB960C-1L22SS
(4)
1K0 1050 858 300
(1)
240 0.2 SIEMENS-MFG_14-193-
101-58-2 (Qty 2)
SIEMENS-MFG_14-193-
101-58-2 (Qty 1)
(4)
(1) No Dynamic Brake Resistor kit available for this drive rating - must be sourced locally.
(2) Coil voltage = 115V AC, 50/60Hz.
(3) See DC Contactor Crimp Lug Kit Specifications on page 259
for more information.
(4) Wire and Lug size dependant on enclosure dimensions and local codes.
Frame
Drive Current
Rating Code
DC
Amps
AC Line
Amps
Hp Dynamic Brake Resistor
Kit Cat. No.
Armature
Voltage
(Volts)
Total DB
Resistance
(ohms)
DC Loop Contactor Cat. No.
(2)
DC Contactor
Crimp Lugs
Cat. No.
(3)
Drive without Dynamic
Brake
Drive with Dynamic
Brake
A 4P1 4.1 3.3 2 1370-DBH63 500 81 1370-NC56 1370-DC56 1370-LG40
6P0 6 4.9 3 1370-DBH64 500 62 1370-NC56 1370-DC56 1370-LG40
010 10 8.2 5 1370-DBH65 500 45 1370-NC56 1370-DC56 1370-LG40
014 14 11.4 7.5 1370-DBH66 500 27 1370-NC56 1370-DC56 1370-LG40
019 19 15.5 10 1370-DBH67 500 20 1370-NC56 1370-DC56 1370-LG40
027 27 22.1 15 1370-DBH68 500 12 1370-NC56 1370-DC56 1370-LG40
035 35 28.6 20 1370-DBH69 500 10 1370-NC56 1370-DC56 1370-LG40
045 45 36.8 25 1370-DBH70 500 9 1370-NC56 1370-DC56 1370-LG52
052 52 42.5 30 1370-DBH71 500 7 1370-NC56 1370-DC56 1370-LG52
073 73 59.6 40 1370-DBH72 500 5.2 1370-NC110 1370-DC110 1370-LG92
086 86 70.3 50 1370-DBH73 500 4 1370-NC110 1370-DC110 1370-LG92
100 100 81.7 60 1370-DBH74 500 4 1370-NC110 1370-DC110 1370-LG110
129 129 105.4 75 1370-DBH75 500 3 1370-NC180 1370-DC180 1370-LG140
B 167 167 136.4 100 1370-DBH76 500 2.1 1370-NC180 1370-DC180 1370-LG180
207 207 169.1 125 1370-DBH77 500 2.1 1370-NC280 1370-DC280 1370-LG228
250 250 204.3 150 1370-DBH78 500 1.5 1370-NC280 1370-DC280 1370-LG268
330 330 269.6 200 1370-DBH79 500 1.05 ABB_EHDB360C2P-1L2S ABB_EHDB360C-1L22SS
(4)
412 412 336.6 250 HUBBELL_Y95W808GB 500 1 ABB_EHDB520C2P-1L2S ABB_EHDB520C-1L22SS
(5)