User Manual

Rockwell Automation Publication 20P-UM001K-EN-P - July 2014 251
Supplemental Drive Information Appendix A
Figure 79 - Frame C Switching Power Supply Circuit Board Fuse Location
Figure 80 - Frame D Switching Power Supply Circuit Board Fuse Location
Frame B Pulse Transformer Circuit Board Fuses
The following fuses are used to protect the MOVs on the pulse transformer
circuit board on frame B drives only.
Circuit Board ID / Revision Designation Fuse (6 x 32 mm)
FIR2-xx / M &below F1/F2/F3 16 A, 500V fast
The switching power supply circuit board is on the back of the control board EMI shield.
F1 = 3.15 A fuse
Rev. “H” and below only.
F2 = 2.5 A fuse
Rev. “H” and below only.
The switching power supply circuit board is on the control panel.
switching power supply fuse holder