User Manual
Rockwell Automation Publication 20P-UM001K-EN-P - July 2014 233
Supplemental Drive Information Appendix A
Table 45 - Frame C Drives Watts Loss and Fan Capacity
Table 46 - Frame D Drives Watts Loss and Fan Capacity
Drive Fans
(2)
(2) Fans on frames C drives must be powered by an external 230 V AC, 50/60 Hz power supply, connected to terminals U3 and V3.
Current Rating
Code
(1)
(1) See Standard Drive Catalog Number Explanation on page 15, positions 8…10 for corresponding drive Hp rating, armature amp rating
and field amp rating.
AC Input
Voltage
Total Watts
Loss
Input Voltage
(VAC)
Rated Current
(A)
Max Air Flow Capacity
Noise Level
521 230 2143
230 0.75
1050 m
3
/h
62.5 dB(A)
700 2700
495 460 2143
667 2590
540 575 2300
675 2620
452 690 1700
565 2300
Drive Fans
(2)
(2) Fans on frames D drives must be powered by an external 230 V AC, 50/60 Hz power supply, connected to terminals U3 and V3.
Current Rating
Code
(1)
(1) See Standard Drive Catalog Number Explanation on page 15, positions 8…10 for corresponding drive Hp rating, armature amp
rating and field amp rating.
AC Input
Voltage
Total Watts
Loss
Input Voltage
(VAC)
Rated Current Max Air Flow Capacity
Noise Level
875 230 2694
230
2.4A@50Hz and
3.3A@60Hz
2400 m
3
/h
80 dB(A)
1K0 3284
830 480 3200
996R 3568
1K1 4189
1K3 5229
1K4 5117
810 575 3122
1K0 3819
1K2 4679
1K3 4879
1K6 5720
678 690 3174
791 3582
904 4028
1K0 4064
1K1 4509
1K2 5368
1K4 5543
1K5 5886