194 Rockwell Automation Publication 20P-UM001K-EN-P - July 2014
Chapter 3 Programming and Parameters
INPUT / OUTPUT
Analog Outputs
66
67
68
69
[Anlg Out1 Sel]
[Anlg Out2 Sel]
[Anlg Out3 Sel]*
[Anlg Out4 Sel]*
Selects the source of the value that drives the analog output.
*This parameter is used to configure an analog output on the
I/O Expansion circuit board. See Appendix F
- Optional Analog and Digital I/O
Expansion Circuit Board.
Note: Option 9 “Torque Ref” was changed to “Sel Torq Ref” for firmware
version 6.001.
Options:
Default:
Default:
Default:
Default:
12 =
13 =
18 =
14 =
“Motor Speed”
“Motor Curr”
“Fld Current”
“Motor Volts”
16-bit
Int
File
Group
No.
Parameter Name & Description
See page 114 for symbol descriptions
Values
Data Type
Related
No. Option (Par) Scaling of Analog Output Value No. Option (Par) Scaling of Analog Output Value
0 = “Off” (Not used) n/a 18 = “Fld Current” (Par 234) 0-10V = 0-100% of Par 280 [Nom Mtr Fld
Amps]
1 = “Spd Ref Out” (Par 385) ±10V = ±100% of Par 45 [Max Ref Speed] 19 = “UserDefined0” (Par 503) ±10V = ±2047 in Par 503 [UserDefined0]
2 = Trim Ramp” (Par 42) ±10V = ±100% of Par 45 [Max Ref Speed] 20 = “UserDefined1” (Par 504) ±10V = ±2047 in Par 504 [UserDefined1]
3 = “Ramp In” (Par 110) ±10V = ±100% of Par 45 [Max Ref Speed] 21 = “UserDefined4” (Par 507) ±10V = ±2047 in Par 507 [UserDefined4]
4 = “Ramp Out” (Par 113) ±10V = ±100% of Par 45 [Max Ref Speed] 22 = “UserDefined5” (Par 508) ±10V = ±2047 in Par 508 [UserDefined5]
5 = “Spd Draw Out” (Par 1018) ±10V = ±100% of Par 45 [Max Ref Speed] 23 = “UserDefined6” (Par 509) ±10V = ±2047 in Par 509 [UserDefined6]
6 = Trim Speed” (Par 43) ±10V = ±100% of Par 45 [Max Ref Speed] 24 = “Field Ref” (Par 500)
(1)
(1) Not used for permanent magnet motor applications.
0-10V = 0-100% of Par 280 [Nom Mtr Fld
Amps]
7 = “Spd Reg In” (Par 118) ±10V = ±100% of Par 45 [Max Ref Speed] 25 = “PID Output” (Par 774) ±10V = ±10000 in Par 774 [PID Output]
8 = “Spd Reg Out” (Par 236) ±10V = ± 100% of Par 179 [Nom Mtr Arm
Amps]
26 = Out Volt Lvl” (Par 921) ±10V = ±100% Par 175 [Rated Motor Volt]
9 = “Sel Torq Ref” (Par 14) ±10V = ± 100% of Par 179 [Nom Mtr Arm
Amps]
27 = “Fld Cur Max” (Par 467) 0-10V = 0-100% of Par 280 [Nom Mtr Fld
Amps]
10 = “Trim Torque” (Par 40) ±10V = ± 100% of Par 179 [Nom Mtr Arm
Amps]
28 = “Filtered Spd” (Par 924) ±10V = ±100% of Par 45 [Max Ref Speed]
11 = “Torq Reg In” (Par 41) ±10V = ± 100% of Par 179 [Nom Mtr Arm
Amps]
29 = “Filtered Cur” (Par 928) ±10V = ± 200% of Par 179 [Nom Mtr Arm
Amps]
12 = “Motor Speed” (Par 121) ±10V = ±100% of Par 45 [Max Ref Speed] 30 = “Output Power” (Par 1052) ±10V = ± 200% of Par 179 [Nom Mtr Arm
Amps] x Par 175 [Rated Motor Volt]
13 = “Motor Curr” (Par 199) ±10V = ± 200% of Par 179 [Nom Mtr Arm
Amps]
31 = “Roll Diam” (Par 1154) 0-10V = 0-100% of Par 1153 [Max Diameter]
14 = “Motor Volts” (Par 233) ±10V = ±100% of Par 175 [Rated Motor Volt] 32 = “Tension Ref” (Par 1180) 0-10V = 0-100% of Par 1153 [Max Diameter]
15 = Analog In 1” (Par 70) ±10V = ±10V on Analog Input 1 33 = “Torque Curr” (Par 1193) ±10V = ± 200% of Par 179 [Nom Mtr Arm
Amps]
16 = Analog In 2” (Par 75) ±10V = ±10V on Analog Input 2 34 = “Winder Ref” (Par 1217) ±10V = ±100% of Par 45 [Max Ref Speed]
17 = Analog In 3” (Par 80) ±10V = ±10V on Analog Input 3 35 = Active Comp” (Par 1213) ±10V = ± 200% of Par 179 [Nom Mtr Arm
Amps]