User Manual

Rockwell Automation Publication 20P-UM001K-EN-P - July 2014 193
Programming and Parameters Chapter 3
INPUT / OUTPUT
Analog Inputs
1045 [Anlg In1 Cmp Eq]
Provides an indication, after the amount of time specified in Par 1044 [Anlg
In1 Cmp Dly] has elapsed, when the value set in parameter 1043 [Anlg In1
Cmp Err] has been reached.
“0” = The value of analog input 1 is above or below the value set in Par
1043 [Anlg In1 Cmp Err].
“1” = The value of analog input 1 is within the range set in Par 1043
[Anlg In1 Cmp Err].
Notes: This parameter can be assigned to a digital output. See Analog Input
Signal Comparison on page 277
for more information.
Default:
Min/Max:
Read Only
0 / 1
16-bit
Int
1042,
1043,
1044
1404 [Analog In1 Value]
Value of the signal at analog input 1. Units based on the value set in Par 71
[Anlg In1 Config].
Default:
Min/Max:
Units:
Read Only
-/+20.00
V or mA
Real 71
1405 [Analog In2 Value]
Value of the signal at analog input 2. Units based on the value set in Par 76
[Anlg In2 Config].
Default:
Min/Max:
Units:
Read Only
-/+20.00
V or mA
Real 76
1406 [Analog In3 Value]
Value of the signal at analog input 3. Units based on the value set in Par 81
[Anlg In3 Config].
Default:
Min/Max:
Units:
Read Only
-/+20.00
V or mA
Real 81
Analog Outputs
62
63
64
65
[Anlg Out1 Scale]
[Anlg Out2 Scale]
[Anlg Out3 Scale]
[Anlg Out4 Scale]
Scaling of the analog outputs.
Default:
Min/Max:
1.00
–/ +10.00
Real
File
Group
No.
Parameter Name & Description
See page 114 for symbol descriptions
Values
Data Type
Related