Chapter 3 Programming and Parameters
COMMUNICATIONS
Masks & Owners
593 [Jog Mask]
Controls which adapters can issue jog commands.
See [Logic Mask]
594 [Direction Mask]
Controls which adapters can issue forward/reverse direction commands.
See [Logic Mask]
595 [Reference Mask]
Controls which adapters can select a manual reference.
See [Logic Mask]
596 [Accel Mask]
Controls which adapters can select the acceleration ramp rates (Pars 660
[Accel Time 1] and 24 [Accel Time 2]) of the drive.
See [Logic Mask] 24,
660
597 [Fault Clr Mask]
Controls which adapters can clear a fault.
See [Logic Mask]
598 [MOP Mask]
Controls which adapters can issue MOP commands to the drive.
See [Logic Mask]
599 [Local Mask]
Controls which adapters are allowed to take exclusive control of drive logic
commands (except stop). Exclusive “local” control can only be taken while
the drive is stopped.
See [Logic Mask]
600 [Stop Owner]
The adapters that are presently issuing a valid stop command. 0 = No Command, 1 = Issuing Command, x = Reserved.
601 [Start Owner]
The adapters that are presently issuing a valid start command.
See [Stop Owner]
602 [Jog Owner]
The adapters that are presently issuing a valid jog command.
See [Stop Owner]
603 [Direction Owner]
The adapter that currently has exclusive control of direction changes.
See [Stop Owner]
604 [Reference Owner]
The adapter that has the exclusive control of the reference source selection.
See [Stop Owner]
605 [Accel Owner]
The adapter that has exclusive control of the acceleration ramp rate (Pars
660 [Accel Time 1] and 24 [Accel Time 2]) for the drive.
See [Stop Owner] 24,
660
606 [Fault Clr Owner]
Adapter that is presently clearing a fault.
See [Stop Owner]
607 [MOP Owner]
Adapters that are currently issuing increases or decreases in MOP
referenced.
See [Stop Owner]
608 [Local Owner]
Adapter that has requested exclusive control of all drive logic functions. If an
adapter is in local lockout, all other functions (except stop) on all other
adapters are locked out and non–functional. Local control can only be
obtained when the drive is not running.
See [Stop Owner]
609 [Decel Owner]
The adapter that has exclusive control of the deceleration ramp rate (Pars
662 [Decel Time 1] and 32 [Decel Time 2]) for the drive.
See [Stop Owner] 32,
662
File
Group
No.
Parameter Name & Description
See page 114 for symbol descriptions
Values
Data Type
Related
Options
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
DPI Port 5
DPI Port 4
DPI Port 3
DPI Port 2
DPI Port 1
Digital In
Default xxxxxxxxxx000000
Bit 1514131211109 8 7 6 5 4 3 2 1 0