User Manual

180 Rockwell Automation Publication 20P-UM001K-EN-P - July 2014
Chapter 3 Programming and Parameters
UTILITY
Diagnostics
1403 [Start Inhibits]
Displays the inputs currently preventing the drive from starting. For each bit, 1=Inhibit condition true and 0=Inhibit condition false.
Faults
263 [Clear Fault Que]
Allows you to clear the fault queue. See Chapter 4 Troubleshooting on page 215 for
information on clearing the fault queue.
Default:
Options:
0 =
0 =
1 =
“Ready”
“Ready”
“Clr Flt Que”
16-bit
Int
1347 [Fault Clear]
Allows you to reset drive faults and/or clear the fault queue.
Default:
Options:
0 =
0 =
1 =
2 =
“Ready”
“Ready”
“Clear Faults”
“Clr Flt Que”
16-bit
Int
1348 [Fault Clr Mode]
Enables/Disables a fault reset (clear faults) attempt from any source. This does not
apply to fault codes which are cleared indirectly via other actions.
Default:
Options:
1 =
0 =
1 =
“Enabled”
“Disabled”
“Enabled”
16-bit
Int
1349 [Status1 at Fault]
Captures and displays Par 381 [Drive Status 1] bit pattern at the time of the last fault. 0=Condition False, 1=Condition True.
381
1350 [Status2 at Fault]
Captures and displays Par 382 [Drive Status 2] bit pattern at the time of the last fault. 0=Condition False, 1=Condition True.
382
1351
1352
1353
1354
1355
1356
1357
1358
1359
1360
[Fault 1 Code]
[Fault 2 Code]
[Fault 3 Code]
[Fault 4 Code]
[Fault 5 Code]
[Fault 6 Code]
[Fault 7 Code]
[Fault 8 Code]
[Fault 9 Code]
[Fault 10 Code]
A code that represents the fault that tripped the drive. The codes will appear in
these parameters in the order they occur (i.e., [Fault 1 Code] = the most recent
fault). See Fault Descriptions on page 218
for a list of possible codes.
Note: Par 1351 [Fault 1 Code] is accessible via the Basic Parameter view.
Default:
Min/Max:
Read Only
0 / 32768
16-bit
Int
File
Group
No.
Parameter Name & Description
See page 114 for symbol descriptions
Values
Data Type
Related
Options
Reserved
Reserved
DPI Port 5
DPI Port 4
DPI Port 3
DPI Port 2
DPI Port 1
Digital In
Reserved
Startup Actv
Reserved
Stop Assertd
Reserved
Enable
Type 2 Alarm
Fault
Default xxx00000x001x000
Bit 1514131211109 8 7 6 5 4 3 2 1 0
Options
Spd Ref ID 3
Spd Ref ID 2
Spd Ref ID 1
Spd Ref ID 0
Local ID 2
Local ID 1
Local ID 0
At Speed
Faulted
Alarm
Decelerating
Accelerating
Actual Dir
Command Dir
Active
Ready
Default 0000111010001100
Bit 1514131211109 8 7 6 5 4 3 2 1 0
Options
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Auto Tuning
Curr Limit
Stopping
Jogging
Running
Active
Ready
Default xxxxxxxxx0001100
Bit 1514131211109 8 7 6 5 4 3 2 1 0
A