User Manual
172 Rockwell Automation Publication 20P-UM001K-EN-P - July 2014
Chapter 3 Programming and Parameters
APPLICATIONS
Scale Blocks
490
559
1224
1233
1242
1251
[Scale1 In Off]
[Scale2 In Off]
[Scale3 In Off]
[Scale4 In Off]
[Scale5 In Off]
[Scale6 In Off]
Offset to be added to the input quantity. Resolution: 5 digits. See the Scale Blocks
block diagram on page 361
for more information.
Default:
Min/Max:
0.00
– 2
31
/ +2
31
– 1
Real
491
560
1225
1234
1243
1252
[Scale1 Out Off]
[Scale2 Out Off]
[Scale3 Out Off]
[Scale4 Out Off]
[Scale5 Out Off]
[Scale6 Out Off]
Offset to be added to the output quantity. Resolution: 5 digits. See the Scale Blocks
block diagram on page 361
for more information.
Default:
Min/Max:
0.00
– 2
31
/ +2
31
– 1
Real
492
561
1226
1235
1244
1253
[Scale1 In Abs]
[Scale2 In Abs]
[Scale3 In Abs]
[Scale4 In Abs]
[Scale5 In Abs]
[Scale6 In Abs]
Controls how the input value is processed.
• “Off” = The input quantity is processed with its sign.
• “On” = The input quantity is processed with a positive sign (absolute value).
It is possible to have the polarity change with the signs of the [ScalexMul] or
[ScalexDiv] parameters. See the Scale Blocks block diagram on page 361
for more
information.
Default:
Options:
0 =
0 =
1 =
“Off”
“Off”
“On”
16-bit
Int
File
Group
No.
Parameter Name & Description
See page 114 for symbol descriptions
Values
Data Type
Related
A
A
A