Programming and Parameters Chapter 3
DYNAMIC CONTROL
Restart Modes
1344 [Start At Powerup]
Enables/Disables the ability to issue a “Run” command and automatically resume
running at commanded speed after drive input power is restored and the time in
Par 1345 [Powerup Delay] has elapsed. Requires a digital input configured for
“Run” and a valid start condition.
Note: See Start At Powerup on page 330
for more information.
Default:
Options:
0 =
0 =
1 =
“Disabled”
“Disabled”
“Enabled”
16-bit
Int
1345
1345 [Powerup Delay]
Defines the programmed delay time, in seconds, before a start command is
accepted after a power up. If a “Start”, “Run” or “Stop” command is asserted before
the time in this parameter expires, the “Start At Powerup” function will be aborted.
Note: See Start At Powerup on page 330
for more information.
Default:
Min/Max:
Units:
1
1 / 10800
s
16-bit
Int
1344
Adaptv Regulator
181 [Adaptive Spd En]
Enables/Disables adaptive speed regulation.
The adaptive speed regulator function enables different gains of the speed
regulator depending on the speed or another variable (Par 183 [Adaptive Ref]).
This allows adaptation of the speed regulator to your specific application. When
adaptive speed regulation is disabled, the regulator operates based on the settings
in the individual regulation parameters.
Note: See Adaptive Speed Regulator on page 317
for more information.
Default:
Options:
0 =
0 =
1 =
“Disabled”
“Disabled”
“Enabled”
16-bit
Int
182,
183
182 [Adaptive Reg Typ]
Selects the type of regulation used.
“Speed” = The regulator parameters follow a speed reference.
Adaptive Ref” = The regulator parameters follow the reference produced by
Par 183 [Adaptive Ref].
Note: See Adaptive Speed Regulator on page 317
for more information.
Default:
Options:
0 =
0 =
1 =
“Speed”
“Speed”
Adaptive Ref
16-bit
Int
183
183 [Adaptive Ref]
The variable reference that the speed regulator parameter will follow when Par
182 [Adaptive Reg Typ] = 1 “Adaptive Ref.
Note: See Adaptive Speed Regulator on page 317
for more information.
Default:
Min/Max:
Units:
1000
–/+6000
rpm
16-bit
Int
182
184 [Adaptive Spd 1]
A percentage of Par 45 [Max Ref Speed] or the maximum value of Par 183
[Adaptive Ref].
Parameter set 1 is valid below the value set in this parameter and parameter set 2
is valid above the value set in this parameter. The transition between the values is
defined by Par 186 [Adaptive Joint 1].
Note: See Adaptive Speed Regulator on page 317
for more information.
Default:
Min/Max:
Units:
20.34
0.00 / 200.00
%
Real 183,
186
185 [Adaptive Spd 2]
A percentage of Par 45 [Max Ref Speed] or the maximum value of Par 183
[Adaptive Ref].
Parameter set 2 is valid below the value set in this parameter and parameter set 3
is valid above the value set in this parameter. The transition between the values is
defined by Par 187 [Adaptive Joint 2].
Note: See Adaptive Speed Regulator on page 317
for more information.
Default:
Min/Max:
Units:
40.69
0.00 / 200.00
%
Real 183,
187
186 [Adaptive Joint 1]
Defines a range above and below the value set in Par 184 [Adaptive Spd 1] within
which there is a linear change in gain from parameter set 1 to parameter set 2 to
prevent jumps in the adaptive speed regulator. The value in this parameter is
defined as percentage of the value defined Par 45 [Max Ref Speed].
Note: See Adaptive Speed Regulator on page 317
for more information.
Default:
Min/Max:
Units:
6.11
0.00 / 200.00
%
Real 184
File
Group
No.
Parameter Name & Description
See page 114 for symbol descriptions
Values
Data Type
Related
ATTENTION: Equipment damage and/or personal injury may result if this parameter is used in an inappropriate
application. Do not use this function without considering applicable local, national and international codes, standards,
regulations or industry guidelines.