MONITOR
Drive Data
465 [Drive Size]
Armature current rating (as indicated by the configuration of DIP switch S15
on the control board). This value is used to determine the Drive Overload fault
(F64).
Note: S15 is set to the appropriate value at the factory. However, if the control
board was supplied separate from the drive and installed as a replacement
part, S15 must be manually set to the appropriate drive size. See DIP Switch
and Jumper Settings on page 75
.
Default:
Min/Max:
Units:
Read Only
0 / Based on drive current rating
A
16-bit
Int
466 [AC Line Voltage]
AC input voltage.
Default:
Min/Max:
Units:
Read Only
0 / 960
Vac
16-bit
Int
588 [AC Line Freq]
AC input frequency.
Default:
Min/Max:
Units:
Read Only
0.00 / 70.00
Hz
Real
1052 [Output Power]
Output power.
Note: This parameter can be assigned to an analog output.
Default:
Min/Max:
Units:
Read Only
0.00 / 9999.99
kW
Real
File
Group
No.
Parameter Name & Description
See page 114 for symbol descriptions
Values
Data Type
Related