User Manual
Rockwell Automation Publication 20P-UM001K-EN-P - July 2014 123
Programming and Parameters Chapter 3
Monitor File
File
Group
No.
Parameter Name & Description
See page 114 for symbol descriptions
Values
Data Type
Related
MONITOR
Speed Meters
44 [Speed Ref A]
Displays the first speed reference of the drive in rpm. This parameter can be
sourced from many signals and is the factory default selection for Par 70
[Anlg In1 Sel]. See block diagram Speed Reference Selection on page 347
for
possible source signals.
Note: The maximum value of this parameter was changed from –/+ Par 45
for firmware version 3.001.
Default:
Min/Max:
Units:
Read Only
–/+ 1.3 x Par 45 [Max Ref Speed]
(1)
rpm
16-bit
Int
45
(1)
The value of [Max Ref Speed] cannot exceed 6000 rpm.
47 [Speed Ref A Pct]
Displays the first speed reference of the drive as a percentage of Par 45 [Max
Ref Speed]. This parameter can be sourced from many signals. See block
diagram Speed Reference Selection on page 347 for possible source signals.
Notes: This parameter can be assigned to an analog input. The min. and max.
values of this parameter were changed from –/+100.0 for firmware version
3.001.
Default:
Min/Max:
Units:
Read Only
–/+130.0
%
Real 45
48 [Speed Ref B]
Displays the second speed reference of the drive in rpm. This parameter can
be sourced from many signals. See block diagram Speed Reference Selection
on page 347
for possible source signals.
Note: The maximum value of this parameter was changed from –/+ Par 45
for firmware version 3.001.
Default:
Min/Max:
Units:
Read Only
–/+ 1.3 x Par 45 [Max Ref Speed]
(1)
rpm
16-bit
Int
45
(1)
The value of [Max Ref Speed] cannot exceed 6000 rpm.
49 [Speed Ref B Pct]
Displays the second speed reference of the drive as a percentage of Par 45
[Max Ref Speed]. This parameter can be sourced from many signals. See block
diagram Speed Reference Selection on page 347 for possible source signals.
Note: The min. and max. values of this parameter were changed from –/
+100.0 for firmware version 3.001.
Default:
Min/Max:
Units:
Read Only
–/+130.0
%
Real 45
110 [Ramp In]
Total reference value input to the ramp in rpm.
Notes: This parameter can be assigned to an analog output. The min. and
max. values of this parameter were changed from –/+32766 for firmware
version 3.001
Default:
Min/Max:
Units:
Read Only
–/+8192
rpm
16-bit
Int
111 [Ramp In Pct]
Total reference value input to the ramp as a percentage of Par 45 [Max Ref
Speed].
Notes: This parameter can be assigned to an analog output. The min. and
max. values of this parameter were changed from –/+100.0 for firmware
version 3.001.
Default:
Min/Max:
Units:
Read Only
–/+200.0
%
Real 45
113 [Ramp Out]
Output of the ramp in rpm.
Notes: This parameter can be assigned to an analog output. The min. and
max. values of this parameter were changed from –/+32766 for firmware
version 3.001
Default:
Min/Max:
Units:
Read Only
–/+8192
rpm
16-bit
Int
114 [Ramp Out Pct]
Output of the ramp as a percentage of Par 45 [Max Ref Speed].
Note: The min. and max. values of this parameter were changed from –/
+100.0 for firmware version 3.001.
Default:
Min/Max:
Units:
Read Only
–/+200.0
%
Real 45
117 [Speed Reg In Pct]
Total reference value input to the Speed Regulator as a percentage of Par 45
[Max Ref Speed].
Notes: This parameter can be assigned to an analog output. The min. and
max. values of this parameter were changed from –/+100.0 for firmware
version 3.001.
Default:
Min/Max:
Units:
Read Only
–/+200.0
%
Real