Owner's manual

22 Rockwell Automation Publication 23P-UM001D-EN-P - July 2012
Chapter 2 Stand Alone Regulator Installation, Wiring and Configuration
Figure 6 - AC /DC Voltage Feedback (KP) and Motor Armature Voltage Feedback
(KA) Terminal Blocks
Table 5 - AC / DC Voltage and Motor Armature Voltage Feedback Terminal
Specifications
DC Feedback Fusing Requirements
The recommended fuses are:
Bussmann fuse FWP-5A14F (5 A, 700V, Type FWP, 14 x 51mm), or
equivalent.
Note: The AC voltage feedback inputs on the SAR are fused internally.
No. Terminal Description
Wire Size Range
Recommended
TorqueMaximum Minimum
W, V, U AC Input
Feedback
(connector KP)
6.0 mm
2
(10 AWG)
0.2 mm
2
(24 AWG)
0.7…0.8 N•m
(6.2…7.1 lb•in)
D, C DC Output
Feedback
(connector KP)
1A1, A1,
1A2, A2
Motor Armature
Voltage Feedback
(connector KA)
1 2 3 4 5 6 7 8
V1 U1 C1 D1
KPT21 KPT11
KPT31
PE
D C W V U
1A1
(C)
A1 1A2
(D)
A2
AC /DC Voltage
Feedback (KP)
Terminal Block
Bottom View of SAR
Motor Armature
Voltage Feedback
(KA) Terminal
Block
1
2
1
1
2