User guide
86 Rockwell Automation Publication 23C-IN001B-EN-P - June 2013
Chapter 2 3 Contactor Full Feature Bypass with Disconnect Package (Style B/N)
Main Fuses (FU1-FU3)
Input line branch circuit protection fuses must be used to protect the input
power lines. If input fuses are not provided with your drive, recommended fuse
values are shown in Ta b le 5
. The input fuse ratings listed in Tab le 5 are applicable
for one drive per branch circuit. No other load may be applied to that fused
circuit.
The recommended fuse type for all PowerFlex Drives for Fan and Pump
Applications is UL Class J, 600V.
Table 5 - Fuse Recommendations
ATTENTION: Most codes require that upstream branch circuit protection be
provided to protect input power wiring. Install the fuses recommended in
Table 5
. Do not exceed the fuse ratings. Failure to observe this precaution could
result in damage to, or destruction of, the equipment.
Drive Rating Fuse Rating
Input Voltage kW Hp Amps
208V AC – 3-Phase 2.2 3.0 20
3.7 5.0 20
5.5 7.5 35
7.5 10 40
11 15 80
15 20 100
18.5 25 125
22 30 150
30 40 200
37 50 250
460V AC – 3-Phase 2.2 3.0 10
4.0 5.0 15
5.5 7.5 20
7.5 10 20
11 15 35
15 20 35
18.5 25 60
22 30 70
30 40 80
37 50 100
45 60 150
55 75 175
75 100 200
90 125 250
110 150 350
132 200 400
160 250 500
200 300 600
250 350 700