Owner manual

Publication 2364P-5.01 December 1999
Appendix A
Specifications
Table A: Functional Specifications
Table B: Environmental Specifications
AC Input Frequency Tolerance 45 to 65 Hz
AC Input Voltage Tolerance ±10%
Overload Capability 150% for 60 sec
Overload Duty Cycle 60 sec every 20 min
Output Voltage Variation 10% max for 100% step load
Resolution of Output Voltage Selection 1.0V
Voltage Regulator Bandwidth 200 rads/sec (nominal)
Current Regulator Bandwidth 1200 rads/sec (nominal)
Minimum Continuous Load Requirement None
Power Factor Near Unity
Efficiency 97%
Shock and Vibration Meets Seizmic Zone 4
Altitude 3,300 ft (1,000 m)
Ambient Temperature 0-40°C (32-104°F)
Relative Humidity 5-95%, non-condensing