3-40 Programming and Parameters
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Advanced Program Group (continued)
A160 [Process Factor] Related Parameter(s): b008
Scales the output frequency value displayed by b008 [Process Display].
Values Default: 30.0
Min/Max: 0.1/999.9
Display: 0.1
Output Freq Process Factor Process Display
=x
A163 [Auto Rstrt Tries] Related Parameter(s): T055, T060, T065, T066, A164
Sets the maximum number of times the drive attempts to reset a fault and restart.
Clear a Type 1 fault and restart the drive.
1. Set A163 [Auto Rstrt Tries] to a value other than “0”.
2. Set A164
[Auto Rstrt Delay] to a value other than “0”.
Clear an OverVoltage, UnderVoltage or Heatsink OvrTmp fault without restarting the drive.
1. Set A163 [Auto Rstrt Tries] to a value other than “0”.
2. Set A164
[Auto Rstrt Delay] to “0”.
Note: If the parameter is not set to zero and [Auto Rstrt Time] is set to zero, auto fault clear is enabled.
This feature automatically clears faults, but does not restart the drive.
Values Default: 0
Min/Max: 0/9
Display: 1
ATTENTION: Equipment damage and/or personal injury may result if this parameter
is used in an inappropriate application. Do not use this function without considering
applicable local, national and international codes, standards, regulations or industry
guidelines.
A164 [Auto Rstrt Delay] Related Parameter(s): A163
Sets the time between restart attempts when A163 [Auto Rstrt Tries] is set to a value other than zero.
Note: If the parameter is not set to zero and [Auto Rstrt Time] is set to zero, auto fault clear is enabled.
This feature automatically clears faults, but does not restart the drive.
Values Default: 1.0 Secs
Min/Max: 0.0/160.0 Secs
Display: 0.1 Secs