Instruction Manual

3-36 Programming and Parameters
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Advanced Program Group (continued)
A147 [Accel Time 2] Related Parameter(s): P039, T051-T054, A143-A146
When active, sets the rate of acceleration for all speed increases. Refer to the flowchart on page 1-29
for details.
Values Default: 30.00 Secs
Min/Max: 0.00/600.00 Secs
Display: 0.01 Secs
Maximum Freq
Accel Time
Accel Rate
=
Speed
0
Time
P035 [Maximum Freq]
P039 or A147
[Accel Time x]
P040 or A148
[Decel Time x]
0
Acceleratio
n
Deceleration
A148 [Decel Time 2] Related Parameter(s): P040, T051-T054, A143-A146
When active, sets the rate of deceleration for all speed decreases. Refer to the flowchart on page 1-29
for details.
Values Default: 30.00 Secs
Min/Max: 0.01/600.00 Secs
Display: 0.01 Secs
Maximum Freq
Decel Time
Decel Rate
=