3-28 Programming and Parameters
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Terminal Block Group (continued)
T086 [Analog Out2 High] Related Parameter(s): P035, T085, T087
Scales the Maximum Output Value for the A065 [Analog Out Sel] source setting.
Examples:
Values Default: 100%
Min/Max: 0/800%
Display: 1%
T086 Setting T085 Setting T085 Max. Output Value
50% 1 “OutCurr 0-10” 5V for 200% Drive Rated Output Current
90% 11 “OutPowr 0-20” 18mA for 200% Drive Rated Power
T087 [Anlg Out2 Setpt] Related Parameter(s): T085, T086
Sets direct parameter control over the analog output. If enabled, this sets the percent value of analog
output.
Values Default: 0.0%
Min/Max: 0.0/100.0%
Display: 0.1%
T088 [Anlg Loss Delay] Related Parameter(s): T069, T070-T076
Sets the length of time after power-up during which the drive will not detect an analog signal loss. The
drive response to an analog signal loss is set in T072
or T076 [Analog In x Loss].
Values Default: 0.0 Secs
Min/Max: 0.0/20.0 Secs
Display: 0.1 Secs
T089 [Analog In Filter]
Sets level of additional filtering of the analog input signals. A higher number increases filtering and
decreases bandwidth. Each setting doubles the applied filtering (1 = 2x filter, 2 = 4x filter, etc.). No
additional filtering is applied when set to “0”.
Values Default: 0
Min/Max: 0/14
Display: 1