Instruction Manual
3-26 Programming and Parameters
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Terminal Block Group (continued)
T083 [Analog Out1 High] Related Parameter(s): P035, T082, T084
Scales the Maximum Output Value for the T082 [Analog Out1 Sel] source setting.
Examples:
Values Default: 100%
Min/Max: 0/800%
Display: 1%
T083 Setting T082 Setting T082 Max. Output Value
50% 1 “OutCurr 0-10” 5V for 200% Drive Rated Output Current
90% 11 “OutPowr 0-20” 18mA for 200% Drive Rated Power
T084 [Anlg Out1 Setpt] Related Parameter(s): T082, T083
Sets direct parameter control over the analog output. If enabled, this sets the percent value of analog
output.
Values Default: 0.0%
Min/Max: 0.0/100.0%
Display: 0.1%