Instruction Manual
3-24 Programming and Parameters
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Terminal Block Group (continued)
T078 [Sleep Level] Related Parameter(s): T077, T079, T080, T081
Sets the analog input level the drive must reach to enter sleep mode.
Values Default: 10.0%
Min/Max: 0.0/100.0%
Display: 0.1%
T079 [Sleep Time] Related Parameter(s): T077, T078, T080, T081
Sets the analog input time the drive must stay below to enter sleep mode.
Values Default: 0.0 Secs
Min/Max: 0.0/600.0 Secs
Display: 0.1 Secs
T080 [Wake Level] Related Parameter(s): T077, T078, T079, T081
Sets the analog input level the drive must reach to wake from sleep mode.
Values Default: 15.0%
Min/Max: 0.0/100.0%
Display: 0.1%
T081 [Wake Time] Related Parameter(s): T077, T078, T079, T080
Sets the analog input time the drive must stay above to wake from sleep mode.
Values Default: 0.0 Secs
Min/Max: 0.0/600.0 Secs
Display: 0.1 Secs