Terminal Block Group (continued)
T074 [Analog In 2 Lo] Related Parameter(s): P034, P038, T072, T073, T075
T076, A152, A153
Stop drive before changing this parameter.
Sets the analog input level that corresponds to P034
[Minimum Freq].
Analog inversion can be accomplished by setting this value larger than T075
[Analog In 2 Hi].
Important: If analog inversion is implemented the drive will go to maximum frequency in the event the
analog input is lost. It is strongly recommended to activate T072
[Analog In 1 Loss] to protect from this
potential occurrence.
Values Default: 0.0%
Min/Max: 0.0/100.0%
Display: 0.1%
0
P035 [Maximum Freq]
P034 [Minimum Freq]
T074 [Analog In 2 Lo] T075 [Analog In 2 Hi]
0
Speed Reference
T075 [Analog In 2 Hi] Related Parameter(s): P035, P038, T073, T074, T076
A152, A153
Stop drive before changing this parameter.
Sets the analog input level that corresponds to P035 [Maximum Freq].
Analog inversion can be accomplished by setting this value smaller than T074 [Analog In 2 Lo].
Values Default: 100.0%
Min/Max: 0.0/100.0%
Display: 0.1%