Instruction Manual

3-20 Programming and Parameters
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Terminal Block Group (continued)
T069 [Analog In 1 Sel] Related Parameter(s): T055, T070, T071, T072
Sets the analog input signal mode (0-20mA, 4-20mA, or 0-10V). This parameter must match DIP
Switch AI1 setting on the control board.
Values Default: 2
Min/Max: 0/6
Display: 1
T069 Option Setting Input Range DIP Switch AI1 Setting
0 Current Mode 0-20 mA 20 mA
1 Current Mode 4-20 mA 20 mA
2 Voltage Mode - Unipolar 0-10V 10V
4 Current Mode (Square Root) 0-20 mA 20 mA
5 Current Mode (Square Root) 4-20 mA 20 mA
6 Voltage Mode - Unipolar (Square Root) 0-10V 10V
T070 [Analog In 1 Lo] Related Parameter(s): P034, P038, T069, T071, T072
A152, A153
Stop drive before changing this parameter.
Sets the analog input level that corresponds to P034
[Minimum Freq].
Analog inversion can be accomplished by setting this value larger than T071 [Analog In 1 Hi].
Important: If analog inversion is implemented the drive will go to maximum frequency in the event the
analog input is lost. It is strongly recommended to activate T072 [Analog In 1 Loss] to protect from this
potential occurrence.
Values Default: 0.0%
Min/Max: 0.0/100.0%
Display: 0.1%
0
P035 [Maximum Freq]
P034 [Minimum Freq]
T070 [Analog In 1 Lo] T071 [Analog In 1 Hi]
0
Speed Reference
T071 [Analog In 1 Hi] Related Parameter(s): P035, P038, T069, T070, T072
A152, A153
Stop drive before changing this parameter.
Sets the analog input level that corresponds to P035 [Maximum Freq].
Analog inversion can be accomplished by setting this value smaller than T070 [Analog In 1 Lo].
Values Default: 100.0%
Min/Max: 0.0/100.0%
Display: 0.1%