Instruction Manual

Programming and Parameters 3-19
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
T065
Options
(Cont.)
16 “Logic In 1” An input is programmed as “Logic In 1” and is active.
17 “Logic In 2” An input is programmed as “Logic In 2” and is active.
24 “Fault” (with FRN 7.xx
and later)
Opto output is inactive when power is applied to the drive and
is active when a fault occurs. This is inverted from Option 0,
“Ready/Fault”.
T066 [Opto Out Level] Related Parameter(s): T065, T068, A163, d318
32 bit parameter.
Determines the on/off point for the opto output when T065
[Opto Out Sel] is set to option 6, 7, 8, 9, 10
or 12.
Values Default: 0.0
Min/Max: 0.0/9999
Display: 0.1
32
T065 Setting T066 Min/Max
6
7
8
9
10
12
0/400 Hz
0/180%
0/815 Volts
0/100%
1/180 degs
0/1
T068 [Opto Out Logic] Related Parameter(s): T065, T066
Determines the logic (Normally Open/NO or Normally Closed/NC) of the opto output.
Note: Setting output to NC may cause output to “glitch” on power-up. The off/reset state of all outputs
is open.
Values Default: 0
Min/Max: 0/1
Display: 1
T068 Option Opto Out Logic
0
1
NO (Normally Open)
NC (Normally Closed)