3-18 Programming and Parameters
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Terminal Block Group (continued)
T065 [Opto Out Sel] Related Parameter(s): P033, T066, T068, T072
T076, A163, d318
Determines the operation of the programmable opto output.
Options 0 “Ready/Fault” Opto output is active when power is applied. This indicates
that the drive is ready for operation. Opto output is inactive
when power is removed or a fault occurs.
1 “At Frequency”
(Default)
Drive reaches commanded frequency.
2 “MotorRunning” Motor is receiving power from the drive.
3 “Hand Active” Active when drive is in local control.
4 “Motor Overld” Motor overload condition exists.
5 “Ramp Reg” Ramp regulator is modifying the programmed accel/decel
times to avoid an overcurrent or overvoltage fault from
occurring.
6 “Above Freq” Drive exceeds the frequency (Hz) value set in T066
[Opto
Out Level].
Use T066 to set threshold.
7 “Above Cur” Drive exceeds the current (% Amps) value set in T066
[Opto Out Level].
Use T066 to set threshold.
Important: Value for T066 [Opto Out Level] must be entered
in percent of drive rated output current.
8 “Above DCVolt” Drive exceeds the DC bus voltage value set in T066
[Opto
Out Level].
Use T066 to set threshold.
9 “Above Anlg 2” Analog input voltage (I/O Terminal 17) exceeds the value
set in T066
[Opto Out Level].
Do not use if T073
[Analog In 2 Sel] is set to 3 “Voltage
Mode - Bipolar”.
This parameter setting can also be used to indicate a PTC
trip point when the input (I/O Terminal 17) is wired to a
PTC and external resistor.
Use T066 to set threshold.
10 “Above PF Ang” Power Factor angle has exceeded the value set in T066
[Opto Out Level].
Use T066 to set threshold.
11 “Anlg In Loss” Analog input loss has occurred. Program T072
[Analog In 1
Loss] and/or T076 [Analog In 2 Loss] for desired action when
input loss occurs.
12 “ParamControl” Enables the output to be controlled over network
communications by writing to T066
[Opto Out Level].
(0 = Off, 1 = On.)
13 “Retries Exst” Value set in A163
[Auto Rstrt Tries] is exceeded.
14 “NonRec Fault” Number of retries for A163
[Auto Rstrt Tries] is exceeded
OR
Non-resettable fault occurs OR
A163
[Auto Rstrt Tries] is not enabled.
15 “Reverse” Drive is commanded to run in reverse direction.