Instruction Manual

Programming and Parameters 3-13
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
T051-
T054
Options
(Cont.)
13 “DCInjStop,CF” The drive immediately begins a DC Injection stop. Can
also be used to clear a fault.
14 “Anlg1 InCtrl”
(1)
Selects Analog Input 1 control for the frequency
reference.
15 “Anlg2 InCtrl”
(1)
Selects Analog Input 2 control for the frequency
reference.
16 “MOP Up” Increases the value of A142
[Internal Freq] at the current
Accel rate if P038
[Speed Reference] is set to 1
“InternalFreq”. Default for A142 is 60 Hz.
17 “MOP Down” Decreases the value of A142
[Internal Freq] at the
current Decel rate if P038 [Speed Reference] is set to 1
“InternalFreq”. Default for A142 is 60 Hz.
18 “Acc & Dec 2”
(1)
When active, A147 [Accel Time 2] and A148 [Decel
Time 2] are used for all ramp rates.
Can only be tied to one input.
Refer to the flowchart on page 1-29
for more information
on Accel/Decel selection.
19 “Current Lmt2” When active, A180
[Current Limit 2] determines the drive
current limit level.
20 “Force DC” If the drive is not running, applying this input causes the
drive to apply a DC Holding current (use A177
[DC Brake
Level], ignoring A176
[DC Brake Time] while the input is
applied.
21 “Mtr I-Lock 1” Can be used as a protective motor interlock in Auxiliary
Motor Control mode. When programmed but not active,
input will prevent corresponding motor from operating.
Refer to Appendix
C for details.
22 “Mtr I-Lock 2”
23 “Mtr I-Lock 3”
24 “Mtr I-Lock 4”
25 “Cmd Reverse” When programmed and active the drive will run in the
reverse direction when started from the integral keypad.
31 “Logic In 1” Input 1 used by digital output settings.
32 “Logic In 2” Input 2 used by digital output settings.
36 “Damper Input” When active, drive is allowed to run normally.
When inactive, drive is forced into sleep mode and is
prevented from accelerating to commanded speed.
(1)
This function may be tied to one input only.