G-4 P1 – Floor Level Network (FLN)
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Table G.2 Point Database for Application 2735
Point Number Subpoint Name Parameter
01 CTLR ADDRESS C104
02 APPLICATION
03 FREQ OUTPUT b001
04 PCT OUTPUT d322
05 SPEED d323
06 CURRENT b003
07 TORQUE b013
08 POWER b010
09 DRIVE TEMP b014
11 DRIVE MWH b011
12 RUN TIME b012
13 DC BUS VOLT b005
20 OVRD TIME
21 FWD.REV MON
22 CMD FWD.REV
23 RUN.STOP MON b066, bit 1 (Running)
24 CMD RUN.STOP
25 READY d302, bit 2 (I/O Terminal 01)
26 RUN ENABLE
29 DAY NGT
30 CURRENT LIMIT P033
31 ACCEL TIME 1 P039
32 DECEL TIME 1 P040
33 KEYPAD LOCK A198
36 READ PARAM #
37 READ VALUE
38 WRITE PARAM #
39 WRITE VALUE
40 DIGITAL OUT 1 T055, T056
41 DIGITAL OUT 2 T060, T061
42 DIGITAL OUT 3 T065, T066
43 OPT RELAY 1 R221, R222 *1
44 OPT RELAY 2 R224, R225 *1
45 OPT RELAY 3 R227, R228 *1
46 OPT RELAY 4 R230, R231 *1
47 OPT RELAY 5 R233, R234 *1
48 OPT RELAY 6 R236, R237 *1
49 DIGITAL IN 1 d302, bit 0 (I/O Terminal 02)
50 DIGITAL IN 2 d302, bit 1 (I/O Terminal 03)
51 DIGITAL IN 3 d302, bit 2 (I/O Terminal 01)
52 DIGITAL IN 4 d302, bit 3 (I/O Terminal 05)
53 DIGITAL IN 5 d302, bit 4 (I/O Terminal 06)
54 DIGITAL IN 6 d302, bit 5 (I/O Terminal 07)
55 DIGITAL IN 7 d302, bit 6 (I/O Terminal 08)
60 INPUT REF 1 d305
61 INPUT REF 2 d306
62 ANALOG OUT 1 T082
63 ANALOG OUT 2 T085
64 LAST FAULT b007
65 PID GAIN A154
66 PID INT TIME A155
67 PID DIFF RATE A156
68 PID SETPOINT A157