F-6 Metasys N2
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Configurable objects are inputs and outputs that let you read and write
parameter values. These objects handle only 16-bit parameter values.
Reading Parameter Values
The configurable points may show any parameter in the drive by
configuring the Param# for INx point. The drive reads the value of the
parameter configured in the Param# for INx point and shows the result in
the User INx point. The Param# for INx’s default to commonly accessed
parameters and can be changed if desired. A “0” disables the fetching of
data and a “0” is returned in the respective User INx. See Figure F.1
and
Table F.13
.
Figure F.1 Configurable Input Point Operation Objects Inputs
Using Metasys Configurable Objects to Access
Parameters
Table F.13 Configurable Objects: Inputs
Network Point
Name Description Default
Type
(NPT)
Address
(NPA)
AI 10 User IN1 User-defined Input 1 0
AI 11 User IN2 User-defined Input 2 0
AI 12 User IN3 User-defined Input 3 0
AI 13 User IN4 User-defined Input 4 0
ADI 1 Param# for IN1 User IN1 (AI 10)
Data Source (Param#)
b001 [Output Freq] (Hz)
ADI 2 Param# for IN2 User IN2 (AI 11)
Data Source (Param#)
b011 [Elapsed MWh]
ADI 3 Param# for IN3 User IN3 (AI 12)
Data Source (Param#)
b012 [Elapsed Run Time]
ADI 4 Param# for IN4 User IN4 (AI 13)
Data Source (Param#)
b014 [Drive Temp]